Outback Power VFX Series Installation Manual

21
AC HOT OUT
AC NEUTRAL OUT
CHASSIS GROUND
NEU/GROUND BOND
AC NEUTRAL IN
AC HOT IN
FULL
OK
LOW
INVERTER
AC IN
BATTERY TEMP
MATE/HUB
INVERTER ON/OFF
INVERTER
ON/OFF
AUX+
AUX-
XCT-
XCT+
REMOVE JUMPER
TO DISABLE
GROUND SWITCHING
BATTERY
STATUS
INVERTER
STATUS
ERROR
AC HOT OUT
Supplies the AC hot output conductors
through a 30 amp maximum AC branch
rated circuit breaker using 10 AWG (.102” or
2.59 mm) wire and connect to the AC
AC NEUTRAL OUT/AC NEUTRAL IN
Connects the AC neutral input conductor to
the AC NEUTRAL IN terminal.
Connects the AC neutral output conductor
to the AC NEUTRAL OUT terminal.
These terminals are common in the Mobile
FX only when an AC source is applied.
The NEUTRAL IN and NEUTRAL OUT
conductors should not be common
(connected in any way) prior to connection
with a Mobile FX
CHASSIS GROUND
Connects both the AC input and AC output
ground conductors to the CHASSIS GROUND
and NEU/GROUND BOND terminals.
If there is only one Mobile FX in the system,
leave the copper bus (provided) installed
between the CHASSIS GROUND and NEU/
GROUND BOND terminals. If there is more
than one Mobile FX in the system, remove
the copper bus from every Slave FX.
AC HOT IN
The AC hot input conductor (black) must be
supplied through a 30 amp maximum AC
branch rated circuit breaker and connected
to the AC HOT IN.
10 AWG (.102” or 2.59 mm) wire is required
for the FX’s AC transfer switch.
AC WIRING NOTES FOR THE MOBILE FX