Outback Power VFX Series Installation Manual

25
SAMPLE INSTALLATIONS
SINGLE FX SYSTEM
All non-Mobile FX AC wiring must handle 60 amps AC or more.
A 60A input breaker must be used for a non-Mobile FX and a 30A input breaker for a Mobile FX.
A single FX can continuously power 2.0kW to 3.6kW of loads depending on which model is used.
GROUND TBB
MECHANICAL
INTERLOCK
INVERTER/CHARGER
AC HOT IN AC HOT OUT
HUB/MATE
60 AMP
BYPASS
BREAKER
30 AMP
OUTPUT
BREAKER
AC NEUTRAL OUT
CHASSIS GROUND
DISPLAY
60 AMP
INPUT
BREAKER
BLACK
BLACK
BLACK
WHITE
GREEN
NOTE:
1. All cables are to be
6AWG THHN or larger.
AC SOURCE
AC LOADS
WHITE
WHITE
AC NEUTRAL IN
WHITE
BLACK
BLACKBLACK
BLACK