Outback Power VFX Series Installation Manual

28
PARALLELED DUAL FX SYSTEM
• All AC wiring from the AC source and to the AC loads must collectively handle 100 amps AC or more.
• All other AC wiring capacity must equal 60 amps AC (Mobile FX units must handle 30 amps AC).
• A paralleled dual FX system can continuously power 4.0 Kw to 7.2kW of loads depending on which
model is used.
NOTE: Program the lowest-installed FX as Master (1-2ph MASTER) and the second FX as an OutBack L1
Slave (OB SLAVE L1)
Parallel/Dual System with Two FXs
GT
Grid-Tie FXs cannot
be used with this
configuration
.