Outback Power VFX Series Installation Manual

29
SERIES/PARALLEL QUAD FX SYSTEM
• All AC wiring from the AC source and to the AC loads must collectively handle 120 amps AC or more.
All other AC wiring must handle a capacity of 60 amps AC (Mobile FX AC wiring must handle 30
amps).
This system can continuously power up to 14.4kW of loads depending on which model is used.
Connecting more power than the continuous rating of the FX may cause breakers to trip or the FX
to shut o its AC output.
A HUB, MATE, and FW-X240 must be connected to successfully stack these FXs in series/parallel.
NOTES:
Program the lowest-installed FX as the Master (1-2ph MASTER), the  rst Slave as an Outback L1 Slave
(OB Slave L1), and the second and third Slaves as OutBack L2 Slaves (OB SLAVE L2) as shown in the
MATE Users Manual.
An FW-X240 Auto Transformer must be used when three or more FXs are series stacked.
When the FXs are connected in series for 120/240VAC, the FW-X240 Auto Transformer can
be connected to the two AC output legs to provide all FX capacity to either of the 120VAC
output circuits. This allows higher e ciency and better performance as heavy 120VAC loads
are powered by all the FXs.
The FW-X240 Auto Transformer also allows the Master to power loads on either of the
120VAC output circuits with the Slave o . This reduces the idle power consumption and
improves the system e ciency.
PARALLELED QUAD FX SYSTEM
All AC wiring from the AC source and to the AC loads must collectively handle 200 amps AC or more.
All other non-Mobile FX Series Inverter/Charger models AC wiring must handle a capacity of 60
amps AC.
This system can continuously power up to 14.4kW of loads depending on which model is used.
Connecting more power than the continuous rating of the FX may cause breakers to trip or the FX
to shut o its AC output.
Refer to Parallel/Dual System drawing on page 28 and expand accordingly.
NOTES: Program the lowest-installed FX as Master (1-2ph MASTER) and the three remaining FXs as
OutBack L1 Slaves (OB SLAVE L1)
GT
Grid-Tie FXs cannot be used with this configuration.
GT
Grid-Tie FXs cannot be used with this configuration.