Outback Power VFX Series Installation Manual

31
3-PHASE FX SYSTEM
This system produces 120VAC per phase and 208VAC from phase to phase. There can only be one FX per phase
on a 3-phase system.
The non-Mobile AC wiring from the AC source and to the AC loads must handle 60 amps AC.
• All other non-Mobile AC wiring must handle a capacity of 60 amps AC; Mobile must handle 30 amps AC.
This system can power continuously up to 10.8kW of loads depending on which model is used.
• Connecting more power than the continuous rating of the FX may cause breakers to trip or the FX to shut o its
AC output.
The jumper in the HUB must be moved for 3-phase con guration (please see the HUB Installation and User
Guide).
NOTE: Program the bottom FX as Master (3ph MASTER) and the two lower FXs as 3-phase Slaves
(3ph SLAVE). Keep the phases in order: phase one is connected to the FX programmed L1; phase
two is connected to L2; and phase three to L3 (or phases A, B, and C to inverters A, B, and C).
GT
Grid-Tie FXs cannot be used with this configuration.