Outback Power VFX Series Installation Manual

47
FX2012MT AC Max = 12AAC (Default = 10AAC) DC Max = 100ADC
FX2524MT AC Max = 14AAC (Default = 12AAC) DC Max = 55ADC
FX2532MT AC Max = 14AAC (Default = 12AAC) DC Max = 40ADC
FX3048T AC Max = 14AAC (Default = 12AAC) DC Max = 35ADC
VFX2812M AC Max = 16AAC (Default = 14AAC) DC Max = 125ADC
VFX3524M AC Max = 20AAC (Default = 18AAC) DC Max = 85ADC
VFX3232M AC Max = 20AAC (Default = 18AAC) DC Max = 60ADC
VFX3648 AC Max = 20AAC (Default = 18AAC) DC Max = 45ADC
AC INPUT FREQUENCY RANGE
NOTE:
If the AC input source is out of the range noted below, the FX will not connect or stay connected.
All FX Models 56 - 64 Hz
MAXIMUM AC OUTPUT CURRENT
This is the amount of surge current that the FX will quickly supply for a split second. Depending on the
size of the surge, the FX can be overloaded for a minimum time of 5 seconds to a maximum time of 30
minutes.
All 12 VDC FXs 56AAC per FX for 1 millisecond
All Other FXs 70AAC per FX for 1 millisecond
MAXIMUM CONTINUOUS OUTPUT POWER
An FX Series Inverter/Chargers model number indicates its maximum continuous output power by
changing the last two digits to zeros. For instance, an FX2012MT has a maximum continuous output
power of 2000VA (volt-amps).
FX2012MT 2000VA (VA = volt-Amps)
FX2024MT 2000VA
FX2532MT 2500VA
FX2548T 2500VA
VFX2812M 2800VA
VFX3524M 3500VA
VFX3232M 3200VA
VFX3648 3600VA
MAXIMUM AND DEFAULT AC INPUT AND DC (bulk stage) OUTPUT VALUES