Outback Power VFX Series Installation Manual

51
FX Model Typical DC
AMPS
NEC AMPS 1-3’ one way 3-5’ one way 5-10’ one way
FX 2012T 167 208 4/0 4/0 4/0
FX2524T
GTFX252
104
104
130
130
2/0 2/0 2/0
FX3048T
GTFX3048
63 78 1/0 1/0 1/0
VFX2812 233 292 4/0 4/0 300 MCM
VFX3524
GVFX3524
146 182 4/0 4/0 4/0
VFX3648
GVFX3648
75 94 1/0 1/0 1/0
MAINTENANCE
If damaged or malfunctioning, the FX should be repaired by a quali ed user, installer, or service center
following OutBack Power Systems instructions and guidelines. Please contact your energy dealer for
assistance. Incorrect repairs and/or reassembly risks malfunction, electric shock or  re.
For routine, user-approved maintenance:
Disconnect all circuit breakers and related electrical connections before doing any cleaning or
adjustments.
Solar modules may produce hazardous voltages when exposed to light; cover them with opaque
material before servicing any connected equipment or service at night.
If a remote or automatic generator start system is used, disable the automatic starting circuit and/or
disconnect the generator from its starting battery while servicing. This will prevent accidental it to
starting or operation.
Recommended Wire Sizes by Length