Installation Manual

Installation
900-0168-01-00 Rev C 19
The inverter’s DC ground is a box lug located next to the negative DC battery terminal. This lug
accepts up to 70 mm (1/0 AWG or 0.109 in) wire. Local codes or regulations may require the DC
ground to be run separately from the AC ground. Also, if present, it will be necessary to remove the
DC Cover or Turbo Fan before making the ground connection. (See page 22.)
Figure 6 DC Ground Lug
Figure 7 Chassis Ground/PE
Box Lug
CHASSIS GROUND/PE
The two CHASSIS GROUND/PE terminals
are electrically common. If connecting to an
external ground bus, only one terminal needs
to be used. The other terminal may be used if
connecting to a device with its own ground
wire, such as a generator.