Installation Guide

Installation
900-0144-01-01 Rev B 35
Figure 31 Parallel AC Wiring with GS Load Centers
1. Ground wiring is not shown for reasons of simplicity. Regardless, this system must be connected to a grounded, permanent wiring
system. See page 19.
2. The Radian inverter has separate neutral connections for grid input, generator input, and output. These are electrically common. If an
external neutral bus exists (as shown in the GSLC), not all of the Radian neutral connections need to be made. In this example, only the
Grid neutral terminal on each inverter is connected.
3. The bypass assembly in each GSLC cannot be used with multiple inverters and is not depicted here. External bypass assemblies are
available from other manufacturers. See pages 10 and 34.
NOTES: