Product Manual

Specifications
900-0145-01-01 Rev B 67
Firmware Revision
This manual applies to inverter models GS7048E and GS3548E with Revision 001.005.xxx or higher.
Updates to the Radian’s firmware are periodically available. These can be downloaded from the
OutBack website www.outbackpower.com. See page 12.
Default Settings and Ranges
NOTE:
Some items are retained at the present setting even when the inverter is reset to factory
defaults. These items are noted with the letter “X” in the Item column.
Certain items, particularly those in the Auxiliary menus, share common set points. If one of these
items is changed in a mode menu, the change will appear in other menus that use the same set point
Certain menus are only visible when the installer password is used, particularly the Grid Interface
Protection menu. These menus are bordered in the table with a double line of this style:
Table 17 Radian Inverter Settings
Field Item Default Minimum Maximum
INVERTER
Hot Key Inverter Mode Off On, Off, or Search
CHARGER
Hot Key Charger Control On On or Off
AC Input
Hot Key AC Input Mode Use Drop or Use
Search
Sensitivity (see page 23 for increments)
10 0 250
Pulse Length
8 AC Cycles 4 AC Cycles 20 AC Cycles
Pulse Spacing
60 AC Cycles 4 AC Cycles 120 AC Cycles
AC Input and
Current Limit
Input Priority Grid Grid or Gen
Grid Input AC Limit
50 Aac 5 Aac 55 Aac
Gen Input AC Limit
50 Aac 5 Aac 55 Aac
Charger AC Limit
GS7048E 30 Aac 0 Aac 30 Aac
GS3548E 15 Aac 0 Aac 15 Aac
Grid AC Input
Mode and Limits
Input Mode Grid Tied
Generator, Support, Grid Tied, UPS, Backup,
Mini Grid, Grid Zero
Voltage Limit Lower
208 Vac 170 Vac 230 Vac
(Voltage Limit) Upper
252 Vac 232 Vac 290 Vac
Transfer Delay
1 second 0.12 seconds 4.0 seconds
Connect Delay
0.2 minutes 0.2 minutes 25.0 minutes
When Mini Grid
mode is selected:
Connect to Grid
48.0 Vdc 44.0 Vdc 64.0 Vdc
(Connect) Delay
10 minutes 2 minutes 200 minutes
When Grid Zero
mode is selected:
DoD Volts
48.0 Vdc 44.0 Vdc 64.0 Vdc
DoD
Amps
GS7048E 5 Aac 1 Aac 30 Aac
GS3548E 5 Aac 1 Aac 15 Aac
Gen AC Input
Mode and Limits
Input Mode Generator
Generator, Support, Grid Tied, UPS, Backup,
Mini Grid, Grid Zero
Voltage Limit Lower
208 Vac 170 Vac 230 Vac
(Voltage Limit) Upper
252 Vac 232 Vac 290 Vac
Transfer Delay
1 second 0.12 seconds 4.0 seconds
Connect Delay
0.5 minutes 0.2 minutes 25.0 minutes
If Mini Grid mode
is selected:
Connect to Grid
48.0 Vdc 44.0 Vdc 64.0 Vdc
(Connect) Delay
10 minutes 2 minutes 200 minutes
If Grid Zero mode
is selected:
DoD Volts
48.0 Vdc 44.0 Vdc 64.0 Vdc
DoD
Amps
GS7048E 5 Aac 1 Aac 30 Aac
GS3548E 5 Aac 1 Aac 15 Aac