Product Manual

Specifications
68 900-0145-01-01 Rev B
Table 17 Radian Inverter Settings
Field Item Default Minimum Maximum
AC Output
Output Voltage
X
230 Vac 200 Vac 260 Vac
AC Coupled Mode
This selection is inoperative
Low Battery
Cut-Out Voltage
42.0 Vdc 36.0 Vdc 48.0 Vdc
Cut-In Voltage
50.0 Vdc 40.0 Vdc 56.0 Vdc
Battery Charger
Absorb Voltage
57.6 Vdc 44.0 Vdc 64.0 Vdc
(Absorb) Time
1.0 hours 0.0 hours 24.0 hours
Float Voltage
54.4 Vdc 44.0 Vdc 64.0 Vdc
(Float) Time
1.0 hours 0.0 hours 24/7
Re-Float Voltage
54.4 Vdc 44.0 Vdc 64.0 Vdc
Re-Bulk Voltage
49.6 Vdc 44.0 Vdc 64.0 Vdc
Battery Equalize
Equalize Voltage
58.4 Vdc 44.0 Vdc 68.0 Vdc
(Equalize) Time
1.0 hours 0.0 hours 24.0 hours
Auxiliary Output
Aux Control Auto Off, Auto or On
Aux Mode Vent Fan
Load Shed, Gen Alert, Fault, Vent Fan, Cool Fan,
DC Divert, GT Limits, Source Status, AC Divert
(Load Shed) ON: Batt >
56.0 Vdc 40.0 Vdc 72.0 Vdc
(Load Shed ON) Delay
0.5 minutes 0.1 minutes 25 minutes
(Load Shed) OFF: Batt <
44.0 Vdc 40.0 Vdc 56.0 Vdc
(Load Shed OFF) Delay
0.5 minutes 0.1 minutes 25 minutes
(Gen Alert) ON: Batt <
44.0 Vdc 40.0 Vdc 56.0 Vdc
(Gen Alert ON) Delay
0.5 minutes 0.1 minutes 25 minutes
(Gen Alert) OFF: Batt >
56.0 Vdc 40.0 Vdc 72.0 Vdc
(Gen Alert OFF) Delay
0.5 minutes 0.1 minutes 25 minutes
(Vent Fan) ON: Batt >
56.0 Vdc 40.0 Vdc 72.0 Vdc
(Vent Fan) Off Delay
0.5 minutes 0.1 minutes 25 minutes
(DC Divert) ON: Batt >
56.0 Vdc 40.0 Vdc 72.0 Vdc
(DC Divert ON) Delay
0.5 minutes 0.1 minutes 25 minutes
(DC Divert) OFF: Batt <
44.0 Vdc 40.0 Vdc 56.0 Vdc
(DC Divert OFF) Delay
0.5 minutes 0.1 minutes 25 minutes
(AC Divert) ON: Batt >
56.0 Vdc 40.0 Vdc 72.0 Vdc
(AC Divert ON) Delay
0.5 minutes 0.1 minutes 25 minutes
(AC Divert) OFF: Batt <
44.0 Vdc 40.0 Vdc 56.0 Vdc
(AC Divert OFF) Delay
0.5 minutes 0.1 minutes 25 minutes
Auxiliary
Relay
Aux Control Auto Off, Auto or On
Aux Mode Gen Alert
Load Shed, Gen Alert, Fault, Vent Fan, Cool Fan,
DC Divert, GT Limits, Source Status, AC Divert
(Load Shed) ON: Batt >
56.0 Vdc 40.0 Vdc 72.0 Vdc
(Load Shed ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Load Shed) OFF: Batt <
44.0 Vdc 40.0 Vdc 56.0 Vdc
(Load Shed OFF) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Gen Alert) ON: Batt <
44.0 Vdc 40.0 Vdc 56.0 Vdc
(Gen Alert ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Gen Alert) OFF: Batt >
56.0 Vdc 40.0 Vdc 72.0 Vdc
(Gen Alert OFF) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Vent Fan) ON: Batt >
56.0 Vdc 40.0 Vdc 72.0 Vdc
(Vent Fan) Off Delay
0.5 minutes 0.1 minutes 25.0 minutes
(DC Divert) ON: Batt >
56.0 Vdc 40.0 Vdc 72.0 Vdc
(DC Divert ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(DC Divert) OFF: Batt <
44.0 Vdc 40.0 Vdc 56.0 Vdc
(DC Divert OFF) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(AC Divert) ON: Batt >
56.0 Vdc 40.0 Vdc 72.0 Vdc
(AC Divert ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(AC Divert) OFF: Batt <
44.0 Vdc 40.0 Vdc 56.0 Vdc
(AC Divert OFF) Delay
0.5 minutes 0.1 minutes 25.0 minutes