Specifications
Electrical Specifications
NOTE
: Items qualified with “default” can be manually changed using the system display.
Table 12 Electrical Specifications for Radian Models
Specification GS8048A GS4048A
Continuous Output Power at 25°C 8000 VA 4000 VA
Continuous AC Output Current at 25°C 33.3 Aac 16.7 Aac
AC Output Voltage (default) 120/240 Vac 120/240 Vac
AC Output Frequency (default) 60 Hz 60 Hz
AC Output Type Split-phase Split-phase
AC Waveform True Sinewave True Sinewave
Typical Efficiency 93% 93%
CEC Weighted Efficiency 92.5% 92.5%
Total Harmonic Distortion (maximum) < 5% < 5%
Harmonic Distortion (maximum single voltage) < 2% < 2%
AC Output Voltage Regulation ± 2% ± 2%
Appliance Protective Class (IEC) Class I Class I
Power Factor –1 to 1 –1 to 1
Inrush Current None None
AC Maximum Output Current (1 ms peak) 100 Aac @240 Vac 50 Aac @240 Vac
AC Maximum Output Current (100 ms RMS) 70.7 Aac @240 Vac 35.35 Aac @240 Vac
AC Overload Capability (100 ms surge) 16.97 kVA 8.48 kVA
AC Overload Capability (5 second) 12.0 kVA 6.0 kVA
AC Overload Capability (30 minute) 9.0 kVA 4.5 kVA
AC Maximum Output Fault Current and Duration
109 Aac for 0.364
seconds
54.5 Aac for 0.364
seconds
Power Consumption (idle) – Invert mode, no load 34 watts 34 watts
Power Consumption (idle) – Search mode 10 watts 10 watts
Power Consumption – Off 4 watts 4 watts
AC Input Voltage Range (L1 or L2) 85 to 140 Vac (L1 or L2) 85 to 140 Vac
AC Input Frequency Range
54 to 66 Hz (60-Hz setting)
45 to 55 Hz (50-Hz setting)
54 to 66 Hz (60-Hz setting)
45 to 55 Hz (50-Hz setting)
AC Input Current (maximum continuous) 50 Aac 50 Aac
Grid-Interactive Voltage Range (default) (L1 or L2) 106 to 132 Vac (L1 or L2) 106 to 132 Vac
Grid-Interactive Frequency Range (default) 59.3 to 60.5 Hz 59.3 to 60.5 Hz
DC Input Voltage (nominal) 48 Vdc 48 Vdc
DC Input Voltage Range 40 to 64 Vdc 40 to 64 Vdc