Product Manual

Specifications
64 900-0161-01-01 Rev B
Table 17 Radian Menu Items
Field Item Default Minimum Maximum
Gen AC Input
Mode and
Limits
Input Mode Generator
Generator, Support, Grid Tied, UPS,
Backup, Mini Grid, GridZero
Voltage Limit
5
Lower 108 Vac 85 Vac 110 Vac
Upper 140Vac 125 Vac 140 Vac
Transfer Delay
5
1.0 second 0.12 seconds 4.0 seconds
Connect Delay
5
0.5 minutes 0.2 minutes 25.0 minutes
If Mini Grid mode
is selected:
Connect to Grid 48.0 Vdc 44.0 Vdc 64.0 Vdc
(Connect) Delay 10 minutes 2 minutes 200 minutes
If Grid Zero mode
is selected:
DoD Volts 48.0 Vdc 44.0 Vdc 64.0 Vdc
DoD
Amps
GS8048A 5 Aac 1 Aac 30 Aac
GS4048A 5 Aac 1 Aac 15 Aac
AC Output
Output Voltage X 120 Vac 100 Vac 130 Vac
Low Battery
Cut-Out Voltage 42.0 Vdc 36.0 Vdc 48.0 Vdc
Cut-In Voltage 50.0 Vdc 40.0 Vdc 56.0 Vdc
Battery
Charger
Absorb Voltage 57.6 Vdc 44.0 Vdc 64.0 Vdc
(Absorb) Time 1.0 hours 0.0 hours 24.0 hours
Float Voltage 54.4 Vdc 44.0 Vdc 64.0 Vdc
(Float) Time 1.0 hours 0.0 hours 24/7
Re-Float Voltage 50.0 Vdc 44.0 Vdc 64.0 Vdc
Re-Bulk Voltage 49.6 Vdc 44.0 Vdc 64.0 Vdc
Battery
Equalize
Equalize Voltage 58.4 Vdc 44.0 Vdc 68.0 Vdc
(Equalize) Time 1.0 hours 0.0 hours 24.0 hours
Auxiliary
Output
Aux Control Auto Off, Auto or On
Aux Mode Vent Fan
Load Shed, Gen Alert, Fault, Vent Fan,
Cool Fan, DC Divert, GT Limits,
Source Status, AC Divert
(Load Shed) ON: Batt > 56.0 Vdc 40.0 Vdc 72.0 Vdc
(Load Shed ON) Delay 0.5 minutes 0.1 minutes 25.0 minutes
(Load Shed) OFF: Batt < 44.0 Vdc 40.0 Vdc 56.0 Vdc
(Load Shed OFF) Delay 0.5 minutes 0.1 minutes 25.0 minutes
(Gen Alert) ON: Batt < 44.0 Vdc 40.0 Vdc 56.0 Vdc
(Gen Alert ON) Delay 0.5 minutes 0.1 minutes 25.0 minutes
(Gen Alert) OFF: Batt > 56.0 Vdc 40.0 Vdc 72.0 Vdc
(Gen Alert OFF) Delay 0.5 minutes 0.1 minutes 25.0 minutes
(Vent Fan) ON: Batt > 56.0 Vdc 40.0 Vdc 72.0 Vdc
(Vent Fan) Off Delay 0.5 minutes 0.1 minutes 25.0 minutes
(DC Divert) ON: Batt > 56.0 Vdc 40.0 Vdc 72.0 Vdc
(DC Divert ON) Delay 0.5 minutes 0.1 minutes 25.0 minutes
(DC Divert) OFF: Batt < 44.0 Vdc 40.0 Vdc 56.0 Vdc
(DC Divert OFF) Delay 0.5 minutes 0.1 minutes 25.0 minutes
(AC Divert) ON: Batt > 56.0 Vdc 40.0 Vdc 72.0 Vdc
(AC Divert ON) Delay 0.5 minutes 0.1 minutes 25.0 minutes
(AC Divert) OFF: Batt < 44.0 Vdc 40.0 Vdc 56.0 Vdc
(AC Divert OFF) Delay 0.5 minutes 0.1 minutes 25.0 minutes
Auxiliary
Relay
Aux Control Auto Off, Auto or On
Aux Mode
Gen Alert
Load Shed, Gen Alert, Fault, Vent Fan,
Cool Fan, DC Divert, GT Limits,
Source Status, AC Divert
(Load Shed) ON: Batt > 56.0 Vdc 40.0 Vdc 72.0 Vdc
(Load Shed ON) Delay 0.5 minutes 0.1 minutes 25.0 minutes
(Load Shed) OFF: Batt < 44.0 Vdc 40.0 Vdc 56.0 Vdc
(Load Shed OFF) Delay 0.5 minutes 0.1 minutes 25.0 minutes
5
These items are not displayed when Grid Tied or Grid Zero modes are in use.