Product Manual

Specifications
66 900-0161-01-01 Rev B
Table 17 Radian Menu Items
Field Item Default Minimum Maximum
Grid Support
(continued)
Low/High
Frequency
Ride-Through
OF2
Freq.
X
60.5 Hz 60.1 Hz 66.0 Hz
Mode Cont. Cont., Mand., Perm., Mom., Cease
Trip 0.16 seconds 0.12 seconds 1000 seconds
OF1
Freq.
X
60.5 Hz 60.1 Hz 66 Hz
Mode Cont. Cont., Mand., Perm., Mom., Cease
Trip 300 seconds 4 seconds 1000 seconds
UF1
Freq.
X
59.3 Hz 50.0 Hz 59.9 Hz
Mode Cont. Cont., Mand., Perm., Mom., Cease
Trip 300 seconds 4 seconds 1000 seconds
UF2
Freq.
X
59.3 Hz 50.0 Hz 59.9 Hz
Mode Cont. Cont., Mand., Perm., Mom., Cease
Trip 0.16 seconds 0.12 seconds 1000 seconds
Fixed Power
Factor
Set Input PF
X
1.00 0.80 1.00
PF Current Lead Lead or Lag
Ramping
Start Ramp
X
250% /min 6% /min 250% /min
Normal Ramp 250% /min 6% /min 250% /min
Frequency Watt
Start Freq
High
X
60.50 Hz 60.05 Hz 65.00 Hz
Low 59.75 Hz 55.00 Hz 59.95 Hz
Gradient
High
X
250% / Hz 5% / Hz 250% / Hz
Low
133% / Hz 5% / Hz 250% / Hz
Re-Start
Freq
High
X
60.50 Hz 60.000 Hz 64.90 Hz
Low 59.85 Hz 55.10 Hz 60.00 Hz
Re-Start Period 1 minute 0 minutes 30 minutes
Volt Watt
Start Volt
High
X
127 Vac 123 Vac 132 Vac
Low 113 Vac 108 Vac 117 Vac
Gradient
High
X
10% / Vac 3% / Vac 100% / Vac
Low
10% / Vac 3% / Vac 100% / Vac
Re-Start
Volt
High
X
125 Vac 122 Vac 130 Vac
Low 114 Vac 110 Vac 118 Vac
Re-Start Period X 1 minute 0 minutes 30 minutes
Volt/VAr
V1 X 106 Vac 98 Vac 124 Vac
V2 X 114 Vac 106 Vac 126 Vac
V3 X 126 Vac 114 Vac 132 Vac
V4 X 132 Vac 116 Vac 142 Vac
Source PF at V1 X 0.90 0.80 1.00
Sink PF at V4 X 0.90 0.80 1.00
Reconnect
Parameters
Reconnect Delay X 300 seconds 0 seconds 600 seconds
High VAC Connect X 132 Vac 115 Vac 144 Vac
Low VAC Connect X 106 Vac 96 Vac 125 Vac
High Freq Connect X 60.5 Hz 60.5 Hz 66.0 Hz
Low Freq Connect X 59.3 Hz 50.0 Hz 59.9 Hz
Multi-Function Parameters
These selections are inoperative
Upload Grid Protection — no settings; used for Grid Support firmware installation