Outback FX-R Series Installation Manual

Commissioning
900-0166-01-01 Rev A
17
Terminals and Ports
Figure 5 Terminals, Ports, and Features
NOTE
:
The
I
NVERTER
O
N
/O
FF
jumper is installed to the
O
N
position during manufacture, but the FXR
inverter is given an external
OFF
command at the same time. Its initial state is Off.
DC and AC
GROUND TERMINALS
These terminals connect to
a grounding system for
both batteries and AC. See
page 18 for instructions.
INVERTER ON/OFF
These terminals receive wires for a manual
on/off switch to control the inverter.
ON/OFF JUMPER
The jumper alongside these terminals
overrides them and turns the inverter on.
(See page 26 for instructions.) With the
jumper installed, a switch cannot turn the
inverter off, but the system display can turn it
off or on. The system display cannot turn it on
if the jumper is not installed.
DC TERMINALS
These terminals connect
to the battery cables and
the DC system.
See page 20 for instructions.
CONTROL WIRING TERMINAL BLOCK
These terminals receive control wires for a
variety of functions including generator control.
See pages 26 and 28 for instructions and the
Operator’s Manual for more information.
The Terminal Block can be unplugged from the
AC board for convenience. While installed,
keep screws tight and the block itself secured
tightly to the AC board to prevent malfunction.
XCT+/XCT-
Non-operational
terminals. Do not
connect anything to them.
MATE/HUB and RTS
PORTS
These ports receive the RJ45
and RJ11 plugs from the
system display and Remote
Temp Sensor. See page 26
for instructions.
The ports are mounted
sideways. When viewed from
the left side, they appear as
shown below.
AC TERMINAL BLOCK
These terminals receive AC
input and output wires. See
page 23 for instructions.
LED INDICATORS
These indicators display the inverter status and battery voltage.
The three B
ATTERY LED indicators (green, yellow, and red) are based
on DC voltage. They provide a very general idea of battery state.
The green I
NVERTER LED indicator shows if the inverting function is on.
The yellow A
C IN LED indicator shows if an AC source is present.
The red E
RROR LED indicator shows either a Warning or an Error.
A Warning is an alert for a problem that is not severe enough for
shutdown. An Error usually accompanies inverter shutdown.
See the Operator’s Manual for more information.
AUX OUTPUT (AUX+/AUX-)
These terminals deliver 12 Vdc up to
0.7 amps (8.4 watts). The output can be
switched on and off for many functions.
The default function is to drive a cooling fan or
the Turbo Fan. See page 26 for details.
The functions for the AUX output can be
programmed using the system display.
AUX LED INDICATOR
Orange LED indicator turns on
when 12 Vdc output is present.