Outback FX-R Series Installation Manual

Commissioning
900-0166-01-01 Rev A
25
ON and OFF Wiring
Figure 15 ON/OFF Jumper and Connections
The
I
NVERTER
O
N
/O
FF
jumper bridges two pins.
This jumper parallels the two
I
NVERTER
O
N
/O
FF
terminals on the Control Wiring Terminal Block.
If either connection is closed, this sets the inverter
to On as long as the internal programming has
not been set to Off with the system display. (The
inverter is given an external
OFF
command in the
factory. Its initial state will be Off.)
An inverter in the Off state will not invert.
However, it may still transfer power to loads and
charge batteries from an AC source.
Jumper Off
If the system display is not present:
To turn the inverter initially On, remove the jumper briefly and then replace it. This requires
long-nose pliers or a similar tool. (This will change the internal programmed state to On.)
After this, removing the jumper will immediately turn the inverter Off.
Once the jumper has been removed, the
I
NVERTER
O
N
/O
FF
terminals on the Control Wiring
Terminal Block can be used to wire a manual on/off switch or an emergency shutoff.
Jumper On