Outback FX-R Series Installation Manual

Installation
28
900-0166-01-01 Rev A
Generator Control
The
A
UX
terminals can provide a signal to control an automatic-start generator. The control
function can be
Advanced Generator Start
(AGS), which is situated in the system display. AGS
can start the generator using settings from the system display, or it can use battery readings from
the FLEXnet DC battery monitor. Note that AGS cannot be used if the system display is removed.
Alternately, the control function can be
Gen Alert
, which is a simpler function based directly in the
FXR inverter. The choice of function depends on system needs and the capabilities of each device.
The generator must be an electric-start model with automatic choke. It is recommended to have
“two-wire” start capability. A two-wire-start generator is the simplest type, where the cranking and
starting routine is automated. It usually has a single switch with two positions that is turned
O
N
to
start,
O
FF
to stop.
Two-Wire Start
The 12 Vdc signal provided by the
A
UX
output can be switched on and off to provide a start
signal. It is possible to send a 12-Vdc signal directly to the generator. However, this should never
be done if it connects the
A
UX
output directly to the generator’s own battery. It is more common to
use the
A
UX
terminals to energize the coil of a 12 Vdc automotive or similar relay.
The OutBack FLEXware Relay Assembly depicted in Figure 19 is sold for this purpose. The relay
contacts can serve in place of the generator’s start switch. The battery shown below ( ) is
depicted for clarity. In most cases the battery is part of the generator’s internal starting circuit and is
not an external component.
The drawing below is one example of a possible arrangement. Specific arrangements, relays, and
other elements depend on the requirements of the installation and of the generator.
Figure 19 Two-Wire Generator Start (Example)
Starting
Terminals
Generator
Battery
Relay
Contacts
Relay
Coil
Two-Wire-Start
Generator
1
1