Product Specifications

2
OutBack reserves the right to make changes to the products and information contained in this document without notice.
Copyright © 2017 OutBack Power. All Rights Reserved. OutBack is a registered trademark of The Alpha Group.
FXR/VFXR A-Series SPECIFICATIONS 04/2017
Models:
Sealed Vented
FXR2012A FXR2524A FXR3048A VFXR2812A VFXR3524A VFXR3648A
Instantaneous Power (100ms)
4800VA 6000VA 6000VA 4800VA 6000VA 6000VA
Surge Power (5 sec)
4500VA 5400VA 5400VA 4500VA 5400VA 5400VA
Peak Power (30 min)
2500VA 3200VA 3200VA 3200VA 4000VA 4000VA
Continuous Power Rating (@ 25°C)
2000VA 2500VA 3000VA 2800VA 3500VA 3600VA
Nominal DC Input Voltage
12VDC 24VDC 48VDC 12VDC 24VDC 48VDC
AC Output Voltage (selectable)
120VAC (100-130VAC) 120VAC (100-130VAC) 120VAC (100-130VAC) 120VAC (100-130VAC) 120VAC (100-130VAC) 120VAC (100-130VAC)
AC Output Frequency (selectable)
60Hz (50Hz) 60Hz (50Hz) 60Hz (50Hz) 60Hz (50Hz) 60Hz (50Hz) 60Hz (50Hz)
Continuous AC Output Current (@ 25°C)
16.7AAC 20.8AAC 25AAC 23.3AAC 29.2AAC 30AAC
Idle Power
Full: ~34W Search: ~9W O: ~3W Full: ~34W Search: ~9W O: ~3W
Typical Eciency
90% 92% 93% 90% 92% 93%
CEC Weighted Eciency
Not applicable Not applicable 91% Not applicable 90.5% 91%
Total Harmonic Distortion
Typical: <2% Maximum: <5% Typical: <2% Maximum: <5%
Output Voltage Regulation
±2.5% ±2.5% ±2.5% ±2.5% ±2.5% ±2.5%
AC Input Voltage Range (MATE3 Adjustable)
85 to 140VAC 85 to 140VAC 85 to 140VAC 85 to 140VAC 85 to 140VAC 85 to 140VAC
AC Input Frequency Range
54 to 66Hz (45 to 55Hz) 54 to 66Hz (45 to 55Hz) 54 to 66Hz (45 to 55Hz) 54 to 66Hz (45 to 55Hz) 54 to 66Hz (45 to 55Hz) 54 to 66Hz (45 to 55Hz)
Grid-Interactive Voltage Range
106 to 132VAC 106 to 132VAC 106 to 132VAC 106 to 132VAC
Grid-Interactive Frequency Range
59.3 to 60.5Hz 59.3 to 60.5Hz 59.3 to 60.5Hz 59.3 to 60.5Hz
Maximum AC Input Current
60AAC 60AAC 60AAC 60AAC 60AAC 60AAC
Continuous Battery Charge Output
100ADC 55ADC 35ADC 125ADC 82ADC 45ADC
Maximum Battery Charging
AC: 14AAC
DC: 100ADC
Power: 1360VA
AC: 14AAC
DC: 55ADC
Power: 1500VA
AC: 14AAC
DC: 35ADC
Power: 1900VA
AC:18AAC
DC: 125ADC
Power: 1700VA
AC: 20AAC
DC: 82ADC
Power: 2230VA
AC: 60AAC
DC: 45ADC
Power: 2450VA
Advanced Battery Charging
Flooded, gel, AGM, lithium-ion and ow chemistry Flooded, gel, AGM, lithium-ion and ow chemistry
DC Input Voltage Range
10.5 to 17VDC 21 to 34VDC 42 to 68VDC 10.5 to 17VDC 21 to 34VDC 42 to 68VDC
Accessory Ports
Remote temperature sensor (included), MATE3 and HUB communications Remote temperature sensor (included), MATE3 and HUB communications
Warranty
Standard 5 year, extended 10 year available Standard 5 year, extended 10 year available
Weight (lb/kg)
Unit: 62 / 29 Shipping: 67 / 30 Unit: 61 / 28 Shipping: 67 / 30
Dimensions H x W x L (in/cm)
Unit: 13 x 8.25 x 16.25 / 21.75 x 13 x 22 Shipping: 21.75 x 13 x 22 / 55 x 33 x 56 Unit: 13 x 8.25 x 16.25 / 21.75 x 13 x 22 Shipping: 21.75 x 13 x 22 / 55 x 33 x 56
Temperature Range
Rated: -20 to 50°C Operating: -40 to 60°C Storage: -40 to 60°C Rated: -20 to 50°C Operating: -40 to 60°C Storage: -40 to 60°C
Relative Humidity Rating
93% 93% 93% 93% 93% 93%
Listings/Certications
UL1741, CSA C22.2 No. 107.1, UL1778, Annex FF UL1741, CSA C22.2 No. 107.1, UL1778, Annex FF
RoHS Compliant
Ye s Ye s Ye s Ye s Ye s Ye s
3.6kVA 3.6kW 3.6kVA
3.06kW
Power Rating Notes
Inverters that specify power in VA but do not use the
unity standard Power Factor (PF) could have misleading
power specications. Volt-Amps (VA) is a total inverter
output, while Watts (W) represent the power consumed by the
electrical loads. PF, which varies by types of loads, is the ratio
of W to VA, and the dierence between the two is power in the
circuit that does no useful work. At 1.0PF (unity), all power is
used. This is the industry-standard used by OutBack Power.
VFXR3648A Power Factor Chart
Power Factor
1.0
0.75
0.5
0.25
0.0
Industry-Standard Non-Industry Standard
0.85
VFXR3648A Power Rating Chart
Power (VA)
8000
6000
4000
2000
0
100ms 5 sec 30 min continuous
Instantaneous Power Rating
Most stringent, massive load start VFXR3648A: 6000VA
Surge Power Rating
Less stringent load start VFXR3648A: 5400VA
Peak Power Rating
Frequent “heavy duty” load requirements VFXR3648A: 4000VA
Continuous Power Rating
Sustained “real world” load requirements VFXR3648A: 3600VA
6000VA
5400VA
4000VA
3600VA
Typical Eciency Rating
Real world eciency with variable loads VFXR3648A: 93%
CEC Eciency Rating
Most stringent US rating VFXR3648A: 91%
VFXR3648A Eciency Rating Chart
Eciency
100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0%
1kVA 2kVA 3kVA 4kVA
91% (CEC)
93% (Typical)