• Two Conductors, 18-gauge shielded stranded must be used for communication. Ground only one end of the
shielded to the earth ground. Use the same earth ground for best ground.
See installation instruction if ASP1 Surge Protector is used.
• Up to eight AeGIS 9000NC can be connected to the Main Relay Control Panel.
DOOR STRIKE OR ELECTRICAL STRIKE
The AeGIS NPB9000 Series provides TWO relay form "C" dry contact: Normally Open (NO) and Normally Closed (NC).
• 10 Ampere 120 VAC or
• 10 Ampere 24 VDC or
• 7 Ampere 250 VAC
See figure 2.1 for door strike wiring diagram. You MUST use two conductors 18 gauge stranded wire minimum.
Note: Some door strikes are creating electrical or magnetic noise or spikes and could create problem to the system's
memory. Although the system's relay has built-in filtration circuit, installing an isolation relay is recommended if the
system is experiencing with looses memory.
POSTAL LOCK
The AeGIS system comes with pre-wired "Normally Open" postal switch as shown on figure 2.2(a). If the postal switch is
pressed, the gate will open. If you need "Normally Closed" postal switch, see figure 2.2(b).
The postal lock is not included. You have to purchase the postal lock from your local post office. See figure 2.2 to alter the
postal switch to normally closed.
MAIN LOBBY PANEL POWER
A 12 VAC 40VA transformer is supplied by Pach and Company. However, 12 VDC 40VA power supply or 12VDC power
supply with battery backup can be used to power the AeGIS 7000NC, use the same connection as shown on figure 2.1.
• Two conductors, 18-gauge wire must be used. See installation instruction if ASP1 Surge Protector is used.
• Do not share power transformer or power supply between the AeGIS 9000NC and other electronic equipment.
• Turn the power "ON" (left position). The Power Light Emitting Diode (LED2) should be "ON". You should see
“Welcome to Pach's Telephone Access Systems" on the Liquid Crystal Display (LCD). If the display is blank, turn
the system off and see Chapter 4.0 Operations and Chapter 6.0 Trouble Shooting Guides.
If 12 VDC 40VA with or without built-in battery backup is used, the output voltage must be
13.5 VDC - 14.0 VDC.
MAIN LOBBY PANEL BATTERY BACKUP
The Main Lobby Panel has a built-in charging circuit for battery backup. The battery will keep the system in full operation dur-
ing power failure. Recommended battery is 12 VDC, 4.5 Ahr rechargeable (customer supply). The life of the battery is
approximately 8 hours in idle mode.