11.3 Piping Length
Piping size
Gas Liquid
Common Length
(m)
Min. Total Length
(m)
Max. Total Length
(m)
Max. Elevation (m) Additional gas
charge amount
(g/m)
3/8” 1/4" 20 6 (3m / indoor unit) 30 x 1 10 20 x 2
Note:
1. It is possible to extend the piping length of one unit up to 20 meters. However, the total piping length must not exceed 30 meters.
2. If the piping length exceeds 20 meters, refrigerant of 20g per meter must be added.