13.2.3 Soft dry operation
13.2.3.1 Thermostat control
Compressor is OFF when intake air temperature – Internal setting temperature <-1.5°C.
Compressor is ON after waiting for 3 minutes, if the intake air temperature – Internal setting temperature >
compressor OFF point.
13.2.4 Heating operation
13.2.4.1 Thermostat control
Compressor is OFF when intake air temperature – Internal setting temperature >+2.0°C.
Compressor is ON after waiting for 3 minutes, if the intake air temperature – Internal setting temperature <
compressor OFF point.
Compressor
OFF
2.5°C
-1.5°
Compressor ON
0.5°
Intake air temperature
– Internal setting temp.