Datasheet

45
Cooling Mode only
Indicator LED
Power e-ion Patrol
Cooling Mode with
e-ion operation
Indicator LED
Power e-ion Patrol
Press e-ion
Press e-ion
Operation stop
Indicator LED
Power e-ion Patrol
e-ion individual operation
Indicator LED
Power e-ion Patrol
Press e-ion
Press e-ion
OFF Timer
activates
Press “OFF/ON”
OFF timer activates
Press “OFF/ON”
OFF timer activates
ON Timer activates
Press “Mode”
LED off
LED on
1
2
4
3
f) Indicator
When Patrol operation starts, Patrol Sensor indicator ON.
When e-ion operation starts based on dirtiness level, e-ion indicator ON.
g) Remote Control Receiving Sound
Normal Operation Æ Patrol Mode : Beep
Patrol Mode Æ Stop : Long Beep
Patrol Mode Æ Normal Operation : Beep
Stop Æ Patrol : Beep
h) Timer Control
When ON timer activates when unit stops, previous operation resumes without Patrol operation.
When ON timer activates during any operation, no change and carry on current operation.
When OFF timer activates during any operation, all operation stops.
i) Power failure
During Patrol individual operation, if power failure occurs, after power resumes, Patrol individual
operation resumes immediately.
During combination operation, if power failure occurs, after power resumes combination resume
immediately.
13.2.15 e-ion Operation
A. Purpose
This operation provides clean air by producing negative ions to attract dust captured at the positively charged e-
ion filters.
B. Control Condition
a) e-ion operation start condition
During unit running at any operation mode, if “e-ion” button is pressed, combination operation (operation
mode + e-ion operation) starts.
During unit is OFF, if “e-ion” button is pressed, e-ion individual operation starts.
b) e-ion operation stop condition
When “OFF/ON” button is pressed to stop the operation.
When “e-ion” button is pressed again.
When “Patrol” button is pressed.
When OFF Timer activates.