Datasheet

50
37°C
38°C
30°C
22°C
17°C
28°C
20°C
Max:70Hz, Min:35Hz
Free
Free
Max:59Hz, Min:16Hz
Min:16Hz
Outdoor air
temperature
15°C
Fixed
Min: 40Hz
48°C
52°C
54°C
50°C
62°C
55°C
Free
Max: 85Hz
Min: 40Hz
8Hz down / 45 sec
COMP = OFF
Indoor heat
exchanger temp.
13.3.2.2 Outdoor air temperature control
The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below. This control will begin 1 minute after the compressor starts.
13.3.2.3 Abnormal Wiring or Piping Connection Checking Control
3 minutes after forced cooling operation was conducted for one room during the initial operation after power was
turned on. The abnormal wiring or piping connection control activates when:
o The outdoor gas piping temperature (connected to non operating indoor unit) drops by more than 5°C to 5°C
or below 3 minutes after compressor started.
o The non operating indoor unit pipe temperature where outdoor air temperature above 5°C has dropped by
more than 20°C to 5°C or lower.
o When above conditions are satisfied, the Timer LED blinks. (H41 error)
13.3.3 Protection Control for Heating Operation
13.3.3.1 Overload Protection Control
The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as
shown in below figures.