Dimensions Guide

Specication Submittal Data / Panasonic Ventilation Fan with Motion Sensor
Description:
Ventilating fan with motion sensor shall be
low sone ceiling mount rated for continuous
operation. Fan shall be ENERGY STAR®
rated and certied by the Home Ventilating
Institute (HVI). Evaluated by the Underwriters
Laboratories and conform to both UL and cUL
standards.
Motor/Blower:
• Four–pole totally enclosed condenser AC
motor rated for continuous use.
• Fan ventilation rates shall be manually
adjustable for 80 or 110 CFM.
• Power Rating shall be 120 volts and 60 Hz.
• Fan shall be UL and cUL listed for tub/shower
enclosure when GFCI protected.
• Motor equipped with thermal cutoff fuse.
• Removable, permanently lubricated, plug-in
motor.
Housing:
• Rust proof epoxy and polyester resin coating,
26 gauge galvanized steel body.
• 4" diameter duct with optional 3" adapter
included.
• Built in backdraft damper.
• Articulating and expandable extension bracket
up to 24".
Grille:
• Attractive design using Poly Pro material.
Attaches directly to housing with torsion springs.
Warranty:
• ALL Parts: For period of 3 years from the date
of the original purchase.
Architectural Specications:
Ventilation fan with motion sensor shall be
ceiling mount, ENERGY STAR® rated with
built-in speed selector. Select from 80/110 CFM
and no more than 0.3/0.8 sone as certied by
the Home Ventilating Institute (HVI) at 0.1 wg
with no less than 71/102 CFM and no more
than 0.8/1.2 sone as certied by HVI at 0.25
w.g. Power Consumption shall be no greater
than 21.6/27.0 watts at 0.1 w.g. and 21.1/26.8
watts at 0.25 w.g. with efciency of no less
than 3.7/4.1 CFM/watt at 0.1 w.g. and 3.3/3.8
CFM/watt at 0.25 w.g. Duct diameter shall be
no less than 4" (3" if using the included duct
adapter). The motor shall be fully enclosed, four
pole condenser type engineered to operate
continuously for no less than 30,000 hours.
Power rating shall be 120v/60Hz. Housing
material shall be no less than 26 gauge
galvanized steel with rust proof epoxy and
polyester resin coating. Fan shall be UL and
cUL listed for tub/shower enclosure when GFCI
protected. Fan can be used to comply with
ASHRAE 62.2, LEED, ENERGY STAR® IAP,
EarthCraft, California Title-24 and WA Ventilation
Code.
FV-08-11VFM5
Panasonic Eco Solutions North America
Eco Products Division
Two Riverfront Plaza
Newark, NJ 07102
us.panasonic.com/ventfans
For complete Installation Instructions visit us.panasonic.com/ventfans
Model Quantity Comments Project:
Location:
Architect:
Engineer:
Contractor:
Submitted by:
Date:
FV-08-11VFM5
3" or 4" Duct
Specications: WhisperFit
®
EZ FV-08-11VFM5
110 CFM Setting 80 CFM Setting
4" Duct 3" Duct 4" Duct 3" Duct
Ventilation Fan
Characteristics
(HVI Certied Data)
Static Pressure in inches w.g. 0.1 0.25 0.1 0.25 0.1 0.25 0.1 0.25
Air Volume (CFM) 110 102 100 88 80 71 70 59
Noise (sones) 0.8 1.2 1.3 1.5 0.3 0.8 0.5 1.1
Power Consumption (Watts) 27.0 26.8 26.8 26.3 21.6 21.1 21.4 20.8
Energy Efciency (CFM/Watt) 4.1 3.8 3.8 3.3 3.7 3.3 3.5 3.0
Speed (RPM) 955 1174 1197 1352 847 1131 1008 1229
Current (amps) 0.23 0.23 0.23 0.22 0.18 0.18 0.18 0.17
MAX. Current (amps) 0.23 0.23 0.18 0.18
Power Rating (V/Hz) 120/60 120/60 120/60 120/60
ENERGY STAR rated YES YES YES YES
0.25=Installed Performance
See Following Page for Performance Curves
®