Specification

Specication Submittal Data / Panasonic Ventilation Fan
Description
Ventilating fan shall be low noise ceiling mount type
rated for continuous run. Fan shall be certied by
the Home Ventilating Institute (HVI). Fan shall also be
evaluated by Underwriters Laboratories and conform
to both UL and cUL safety standards.
Motor/Blower:
• Four–pole fully enclosed condenser motor rated for
continuous run.
• Power rating shall be 120 volts and 60 Hz.
• Fan shall be UL listed for tub/shower enclosure
when GFCI protected and used in insulated ceiling
(TYPE I.C.).
• Motor equipped with thermal–cutoff fuse.
• Removable with permanently lubricated plug–in
motor.
Housing:
• Rust proof paint, galvanized steel body.
• 6" diameter duct adapter.
• Built-in metal ange provides blocking for
penetrations through drywall as an Air Barrier, and
assists wtih the decrease in the leakage in the
Building Envelope during blower door testing.
• Built in backdraft damper.
• Double hanger bar system allowing for ideal
positioning.
• Expandable extension bracket up to 26".
Grille:
• Attractive design using Poly Pro material.
• Attaches directly to housing with torsion springs.
Warranty:
• ALL Parts: 3 years from original purchase date.
Architectural Specications:
Ventilating fan shall be ceiling mount, with no less
than 390 CFM and no more than 3.0 sones as
certied by the Home Ventilating Institute (HVI) at
0.1 wg and no less than 356 CFM and no more
than 3.0 sones at .25 wg. Power consumption shall
be no greater than 111.4 Watts at .1 wg and 109.6
Watts at .25 wg. Energy efciency shall be no less
than 3.5 CFM/Watt at .1 wg and 3.3 CFM/Watt at
.25 wg. The motor shall be fully enclosed, four pole
condenser type engineered to operate continuously.
Power rating shall be 120v/60Hz. Duct diameter shall
be no less than 6". Fan shall be UL and cUL listed
for tub/shower enclosure when GFCI protected. Fan
can be used to comply with ASHRAE 62.2, LEED,
EarthCraft, California Title-24, and WA Ventilation
Code.
FV-40VQ4
Panasonic Eco Solutions North America
Eco Products Division
Two Riverfront Plaza
Newark, NJ 07102
us.panasonic.com/ventfans
Specications: WhisperCeiling FV-40VQ4
6" Duct
Static Pressure in inches w.g. 0.1 0.25
Air Volume (CFM) 390 356
Noise (sones) 3.0 3.0
Power Consumption (watts) 111.4 109.6
Energy Efciency (CFM/Watt) 3.5 3.3
Speed (RPM) 793 874
Current (amps) 0.99 0.98
ENERGY STAR NO
For complete Installation Instructions visit us.panasonic.com/ventfans
Model Quantity Comments Project:
Location:
Architect:
Engineer:
Contractor:
Submitted by:
Date:
FV-40VQ4
6" duct
VF15944SS
Performance Curve
0.00
0.20
0.40
0.60
0.80
1.00
1.20
1.40
1.60
0 100 200 300 400
Static Pressure(inch w.g.)
Airflow(CFM)
FV-40VQ4
20 Feet
40 Feet
60 Feet
80 Feet
100 Feet
6" Duct