8-2 Peripheral Device Configuration
8-2-1 Installation Environment
Use the servo amplifier under the environment of pollution level 2 or 1 defined in IEC60664-1.
(Example: Installed in the IP54 control panel.)
8-2-2 Power Supply
200V system : Single 220V - 240V 50/60Hz
(1) Use it under the environment of overvoltage category II defined in IEC60664-1.
(2) As for the interface power supply, use the CE marking conforming product or the 12-24 VDC power supply
of insulation type compliant with EN standard (EN60950).
8-2-3 Circuit Breaker
Make sure to connect a circuit breaker compliant with IEC standard and UL certification
(marked with LISTED ) between the power supply and the noise filter.
Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be
provided in accordance with the National Electrical Code and any additional local codes.
8-2-4 Noise Filter
To install one noise filter as a whole in the power unit when multiple servo amplifiers are used, consult the noise
filter manufacturer.
8-2-5 Surge Absorber
Install the surge absorber in the primary side of the noise filter.
Please!
To carry out a pressure test of equipments and devices, make sure to detach the surge absorber.
Otherwise, the surge absorber can be damaged.