Operating Instructions Air-to-Water Heatpump Model No. Indoor Unit WH-SDC0509L3E5 WH-SDC0509L6E5 Outdoor Unit WH-WDG05LE5 WH-WDG07LE5 WH-WDG09LE5 ENGLISH Before operating the system, please read these operating instructions thoroughly and keep them for future reference.
Thank you for purchasing Panasonic product. Installation Instructions attached. Serial number and production year please refer to name plate. Table of contents System overview, Operating conditions ............................3 Safety precautions .......................................................4-16 Protective zone ...............................................................17 Remote Controller buttons and display .....................18-19 Initialization ..........................................
Before use, make sure the system has been installed correctly by an authorised dealer according to the given instructions. • Panasonic Air-to-Water Heatpump is a split system, consisting of two units: indoor and outdoor units. This system is designed to operate with Panasonic Water Tank Unit. Unless used together with the Panasonic Water Tank Unit, Panasonic does not guarantee any normal operation nor the reliability of the system.
Safety precautions To prevent personal injury, injury to others or property damage, please comply with the following: Incorrect operation due to failure to follow instructions below may cause harm or damage, the seriousness of which is classified as below: WARNING This sign warns of death or serious injury. CAUTION This sign warns of injury or damage to property. The instructions to be followed are classified by the following symbols: This symbol denotes an action that is PROHIBITED.
Do not insert your fingers or other objects into the Air to water indoor or outdoor unit, rotating parts may cause injury. It is strongly recommended that Install Residual Current Device (RCD) on-site to prevent electric shock and/ or fire. Do not touch the outdoor unit during lightning, it may cause electric shock. Before obtaining access to terminals, all supply circuits must be disconnected. Do not sit or step on the unit, you may fall down accidentally. Do not install the indoor unit outdoors.
Safety precautions CAUTION Indoor unit and outdoor unit Do not wash the indoor unit with water, benzine, thinner or scouring powder to avoid damage or corrosion at the unit. Do not install the unit close to any combustibles or at bathroom. Otherwise, it may cause electric shock and/or fire. Precautions shall be taken to avoid excessive vibration or pulsation to Water piping. Protect the Water piping from accidental rupture due to moving furniture or reconstruction activities.
WARNING This appliance is filled with R290 (Extremely flammable gas, safety A3 group per ISO 817). If the refrigerant is leaked and exposed to an external ignition source, there is a risk of fire. Indoor unit and outdoor unit Protective zone is defined near the product. See section Protective zone. Be aware that refrigerant may not contain an odour, highly recommended to ensure suitable flammable refrigerant gas detectors are present, operating and able to warn of a leak.
Safety precautions • Before a new refrigerating system is put into service, the person responsible for placing the system in operation should ensure that trained and certified operating personnel are instructed on the basis of the instruction manual about the construction, supervision, operation and maintenance of the refrigerating system, as well as the safety measures to be observed, and the properties and handling of the refrigerant used.
2. Servicing 2-1. Service personnel • The system is inspected, regularly supervised and maintained by a trained and certified service personnel who is employed by the person user or party responsible. • Ensure refrigerant charge not to leak.
Safety precautions 2-3. Checking for presence of refrigerant • The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres. • Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. non sparking, adequately sealed or intrinsically safe. • In case of leakage/spillage happened, immediately ventilate area and stay upwind and away from spill/release.
2-7. Checks to the refrigerating equipment • Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. • At all times the manufacturer’s maintenance and service guidelines shall be followed. • If in doubt consult the manufacturer’s technical department for assistance. • The following checks shall be applied to installations using flammable refrigerants. -The ventilation machinery and outlets are operating adequately and are not obstructed.
Safety precautions 3. Repairs to sealed components • During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. • If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
7. The following leak detection methods are deemed acceptable for all refrigerant systems • No leaks shall be detected using detection equipment with sensitivity to detect leakage of 5g/year of refrigerant or better under a pressure of at least 0.25 times the maximum allowable pressure (>0.98 MPa, max 3.90 MPa), for example, a universal sniffer. • Electronic leak detectors may be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need recalibration.
Safety precautions • Ensure that the outlet for the vacuum pump is not close to any potential ignition sources and there is ventilation available. 9. Charging procedures • In addition to conventional charging procedures, the following requirements shall be followed. -Ensure that contamination of different refrigerants does not occur when using charging equipment. -Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them.
h) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off. • Electrostatic charge may accumulate and create a hazardous condition when charging or discharging the refrigerant. To avoid fire or explosion, dissipate static electricity during transfer by grounding and bonding containers and equipment before charging/discharging. 11.
Safety precautions • Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt. • The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged.
Protective zone This outdoor unit is filled with R290 (Extremely flammable gas, safety A3 group per ISO 817). Note that this refrigerant has a higher density than air. In case of a refrigerant leak, the leaked refrigerant may accumulate near the ground. Prevent accumulation of refrigerant in any way that is potentially dangerous, explosive or risk suffocation. Prevent refrigerant from entering the building through building openings. Prevent accumulation of refrigerant in the drain grooves.
Remote Controller buttons and display B The LCD display as shown in this manual are for instructional purpose only, and may differ from the actual unit. C D Buttons / Indicator 1 Quick Menu button Back button Returns to the previous screen LCD Display 3 (Actual - Dark background with white icons) Main Menu button 4 For function setup ON/OFF button 5 Starts/Stops operation Operation indicator 6 Illuminates during operation, blinks during alarm. When the backlight is off, press any button to turn it on.
Display A Mode selection *1, *2 AUTO • Depending on the preset outdoor *1, *2 COOL temperature, the system selects HEAT or *1, *2 COOL operation mode. Auto Heat *1, *2 AUTO + *3 TANK HEAT + *3 TANK Auto Cool • Depending on the preset outdoor *1, *2 COOL temperature, the system selects + *3 TANK HEAT + TANK or *1, *2 COOL + TANK operation mode. Auto Heat HEAT • COOL operation is either turned ON or OFF. • The outdoor unit provides cooling to the system.
Initialization Before starting to install the various menu settings, please initiate the Remote Controller by selecting the language of operation and installing the date and time correctly. When power is turned on for the first time, it becomes the setting screen automatically. It can also be set from personal setting of the menu. Selecting the language LCD blinking Wait while the display is initializing. When initializing screen ends, it turns to normal screen.
Quick Menu After the initial settings have been completed, you can select a quick menu from the following options and edit the setting. 1 to display the quick menu. Press 2 Use 3 Press to select menu. to turn on/off the select menu. Quick Menu *1 Force DHW Powerful Quiet Force Heater Weekly Timer Force Defrost Error Reset R/C Lock Select each setting and confirm the setting according to the instructions displayed at the bottom of the screen. (The icons refer to each selection key.
How to use the Quick Menu Force DHW Select this icon to turn the Tank DHW on or off. Press to confirm your selection. • Force DHW is turned off. • Force DHW is turned on. Note: • Force DHW is disabled when Force Heater is turned on. • When Force DHW is turned off, operation & mode should change back to the previous memorized status. Powerful Select this icon to operate the heating/cooling system powerfully. Press to confirm your selection.
Quiet Select this icon to operate quietly. to confirm your selection. Press (The quiet operation starts approximately 1 minute after is pressed.) • Quiet mode is set off. • The Quiet mode operates at level 1. • The Quiet mode operates at level 2. • The Quiet mode operates at level 3. Level 3 is the most quiet mode. • Select this to set a timer for the Quiet mode operation. After 1 sec delay. Select “Yes”. • Select “Yes” using buttons. Select pattern “1” ~ “6”. Select “Edit”.
How to use the Quick Menu Force Heater Select to force the Heater on. to confirm your selection. Press (The Force Heater mode starts approximately 1 minute after is pressed.) • Force Heater is turned off. • Force Heater is turned on. Note: • Force Heater is disabled whenever operation is already on and “Disabled due to operation ON!” will be displayed.
Weekly Timer Select this icon to delete (cancel) or change the pre-set Weekly Timer. Press to confirm your selection. • Timer is not ON. • Timer is set. Select “Yes”. • If you select “No”, the screen will return to the Quick Menu Screen. • Timer setup: Select Timer setup to edit the Weekly Timer. • Timer copy: Select to copy a timer setting. [Example of a Timer setup] Select the day(s) which you wish to edit using buttons. If all 6 patterns are not preset, this screen will be displayed.
How to use the Quick Menu Force Defrost Select to defrost the frozen pipes. to confirm your selection. Press (When the mode is accepted, below screen will be displayed.) Error Reset Select to restore the previous settings when error has occurred. Press to confirm your selection. (When the mode has been accepted, below screen will be displayed.) • Make sure all units are turned off before selecting this mode which restores the whole system to the previous settings.
Menus For user Select menus and determine settings according to the system available in the household. All initial settings must be done by an authorised dealer or a specialist. It is recommended that all alterations of the initial settings are also done by an authorised dealer or a specialist. • After initial installation, you may manually adjust the settings. • The initial setting remains active until the user changes it. • The Remote Controller can be used for multiple installations.
Menus For user Menu 1.4 Default Setting Quiet priority • To select priority during Quiet mode between Sound and Capacity. • If Sound priority is selected, unit will operate in quiet condition only. • If Capacity priority is selected, unit will operate in quiet condition but it will prioritize on providing required capacity at the same time. 1.5 Capacity OFF *1 Tank heater To set the tank heater ON or OFF. 1.7 Sound Sound Room heater To set the room heater ON or OFF. 1.
Menu Default Setting 2 System check Energy monitor 2.1 Present or historical chart of energy consumption, generation or COP. Setting Options / Display Present Select and retrieve Historical chart Select and retrieve • COP= Coefficient of Performance. • For historical chart, the period is selected from 1 day/1 week/1year. • Energy consumption (kWh) of heating, *1, *2 cooling, *3 tank and total may be retrieved.
Menus For user Menu Default Setting Setting Options / Display 3 Personal setup Remote control No. 3.1 • To display remote control number of a particular remote controller so that installer and end user are well informed. • Main remote controller is displayed as RC-1. Second remote controller is displayed as RC-2. 3.2 10:34am,Mon RC-1 Select and retrieve Confirm Touch sound Turns the operation sound ON/ OFF. 3.3 RC No. ON LCD contrast Sets the screen contrast. 3 3.
Menu 3.8 Default Setting Language Sets the display language for the top screen. 3.9 Setting Options / Display ENGLISH / FRANÇAIS / DEUTSCH / ITALIANO / ESPAÑOL / DANISH / SWEDISH / NORWEGIAN / POLISH / CZECH / NEDERLANDS / TÜRKÇE / SUOMI / MAGYAR / SLOVENŠČINA / HRVATSKI / LIETUVIŲ / PORTUGUÊS / БЪЛГАРСКИ / EESTI / LATVIEŠU / ROMÂNĂ / SHQIP / SLOVENČINA / МАКЕДОНСКИ / УКРАЇНСЬКА / ΕΛΛΗΝΙΚΑ Unlock password 4 digit password for all the settings. 0000 4 Service contact Contact 1 / Contact 2 4.
Menus For installer Menu Default Setting Setting Options / Display 5 Installer setup System setup Optional PCB connectivity 5.1 To connect to the external PCB required for servicing. No • If the external PCB is connected (optional), the system will have following additional functions: 1 Control over 2 zones (including the swimming pool and the function to heat water in it). 2 Solar function (the solar thermal panels connected to either the DHW (Domestic Hot Water) Tank or the Buffer Tank.
Menu 5.6 5.7 Default Setting DHW capacity To select tank heating capacity to variable or standard. Variable capacity heat up tank with fast mode and keep the tank temperature with efficient mode. While standard capacity heat up tank with rated heating capacity. Setting Options / Display Variable Buffer tank connection To connect tank to the system and if selected YES, to set T temperature.
Menus For installer Menu 5.11 Default Setting Setting Options / Display Bivalent connection To select to enable or disable bivalent connection. No Yes To select either auto control pattern or SG ready input control pattern or smart control pattern. - This selection only display to select when optional pcb connection set to Yes.
Menu Default Setting Setting Options / Display -8 °C Set the temperature threshold to start the bivalent heat source. 0:30 Delay timer to start the bivalent heat source (in hour and minutes). -2 °C Set the temperature threshold to stop the bivalent heat source. 0:30 Delay timer to stop the bivalent heat source (in hour and minutes). Control pattern Advanced parallel DHW Yes • DHW Tank is activated only after selecting “Yes”.
Menus For installer Menu To do settings related to electricity and boiler so that unit is able to determine whether to operate heat pump or boiler at a particular period depends on operating cost of both heat sources. These settings are electricity price, boiler price, season, schedule etc. Default Setting Setting Options / Display Yes Smart Option to set external pump either ON or OFF during bivalent OFF operation. Set to ON if system is simple bivalent connection.
Menu Default Setting Setting Options / Display Yes Smart After selecting for the external pump Schedule Season setting Bivalent connection 10:34am,Mon Season 1 : Dec (Refers to Winter Schedule season) Season setting Season 2 : Mar (Refers to Spring Schedule setting season) Season 3 : Jun (Refers to Summer Select Confirm season) Season 4 : Oct (Refers to Autumn season) Bivalent connection 10:34am,Mon - There are total 4 seasons to be set Season 1: Start month - Set the starting month for each Range: (Jan~
Menus For installer Menu Default Setting Setting Options / Display - Range of start time displayed can be in “24h” or “am/pm” format depend on setting of “Clock format”. Season 1 Range: (0.00~23.00) Steps: ±1hour Select - Range of electricity price is 0 ~ 10 which refers back to the 10 different electricity price set previously (under “Energy price > Electricity”: Electricity price 1 ~ Electricity price 10).
Menu Default Setting Setting Options / Display Yes After selecting the tank 5 °C Set T OFF temperature Yes After selecting the tank 5 °C T ON temperature T ON temperature Set Antifreeze temperature Yes After selecting the tank T ON temperature After setting the antifreeze temperature 80 °C 5.14 T OFF temperature T OFF temperature Set Hi limit External error signal No 5.15 Demand control No 5.16 SG ready No Yes 120 % 5.
Menus For installer Menu 5.19 Default Setting Setting Options / Display Heat-Cool SW No 5.20 Force heater To turn on Force heater either manually (by default) or automatically. 5.21 Force defrost If auto selection is set, outdoor unit will start defrost operation if long heating hour operate during low outdoor temperature. 5.22 Yes Heating control To select unit operation condition whether to achieve set temperature faster or to save energy.
Menu 5.26 Default Setting Setting Options / Display External meter To set which external meter to be used depends on meter connection. There are generation meters and various types of electricity meters. For generation meters, there are two connection systems :a) One generation meter system : Heat-cool meter only b) Two generation meter system : Heat-cool meter and Tank meter Heat-cool meter : No * Tank meter : No Elec. meter HP : No Elec. meter 1 (PV) : No Elec. meter 2 (Building) : No Elec.
Menus For installer Menu Default Setting Setting Options / Display Elec. meter 3 (Reserve) - Set Elec. meter 3 (Reserve) to Yes when this electricity meter is connected. - It is to measure energy consumption. This data will be displayed only on Cloud system. Remark : Elec. stands for “Electricity” HP stands for “Heat pump” 5.27 *1 Electrical anode To enable or disable operation of electrical anode. *1 It is used when supplying power to the electric anode of optional parts from inside the equipment.
Menu Default Setting Setting Options / Display 6 Installer setup Operation setup To access to the four major functions or modes. 4 main modes Heat / *1, *2 Cool / *1, *2 Auto / *3 Tank 6.1 Heat To set various water & ambient temperatures for heating. Water temp. for heating ON / Outdoor temp. for heating OFF / T for heating ON / Heater ON/OFF Water temp. for heating ON Compensation curve Heating ON temperatures in compensation curve or direct input. Water temp.
Menus For installer Menu Default Setting Setting Options / Display Outdoor temp. for heating OFF 24 °C Temperature for heating OFF T for heating ON 5 °C Set T for heating ON. * This setting will not available to set when pump flowrate set to Max. duty. Heater ON/OFF Heater ON/OFF Outdoor temp.
Menu Default Setting Setting Options / Display Water temp. for cooling ON Compensation curve Cooling ON temperatures in compensation curve or direct input. Water temp. for cooling ON Compensation curve X axis: 20 °C, 30 °C Y axis: 15 °C, 10 °C Input the 4 temperature points (2 on horizontal X axis, 2 on vertical Y axis) • If 2 zone system is selected, the 4 temperature points must also be input for Zone 2. • “Zone 1” and “Zone 2” will not appear on the display if only 1 zone system. Water temp.
Menus For installer Menu Default Setting Setting Options / Display Outdoor temp. for (Cool to Heat) 10 °C 6.4 Set outdoor temperature for switching from Cool to Heat. *1 Tank Setting functions for the tank. Floor operation time (max) / Tank heat up time (max) / Tank re-heat temp. / Sterilization • The display will show 3 functions at a time.
Menu Default Setting Setting Options / Display Sterilization: Boiling temp. Set boiling temperatures for sterilize the tank. 65 °C Sterilization: Ope. time (max) Set sterilizing time (in hours and minutes) 0:10 7 Installer setup Service setup Pump maximum speed 7.1 To set the maximum speed of the pump. Setting the flow rate, max. duty and operation ON/OFF of the pump. Flow rate: XX:X L/min Max. Duty: 0x40 ~ 0xFE, Pump: ON/OFF/Air Purge 7.2 Dry concrete To dry the concrete (floor, walls, etc.
Menus For installer Menu 7.3 Default Setting Setting Options / Display Service contact To set up to 2 contact names and numbers for the User. Service engineer’s name and contact number. Contact 1 / Contact 2 Contact 1 / Contact 2 Contact name or number. Name / phone icon Input name and number Contact name: alphabet a ~ z. Contact number: 1 ~ 9 8 Installer setup Remote control setup • To select whether to use one remote controller or two remote controllers.
Cleaning instructions To ensure optimal performance of the system, cleaning has to be carried out at regular intervals. Consult an authorised dealer. • Disconnect the power supply before cleaning. • Do not use benzine, thinner or scouring powder. • Use only soap ( pH7) or neutral household detergent. • Do not use water hotter than 40 °C. Regular Checks Indoor unit • Do not splash water directly. Wipe the unit gently with a soft dry cloth.
Cleaning instructions Maintenance FILLING THE CIRCUIT SYSTEM If the pressure is too low in the CIRCUIT system, it needs to be topped up. See the Installer Manual for more information. VENTING THE CIRCUIT SYSTEM In event of repeated filling of the CIRCUIT system, or if bubbling sounds are heard from the indoor module, the system may need venting. This is done as follows: 1. Turn off the power supply to the indoor module. 2.
Troubleshooting The following symptoms do not indicate malfunction. Symptom Cause Water flowing sound during operation. Operation is delayed a few minutes after restarting. Outdoor unit emits water/steam. Steam comes out of the outdoor unit in the heating mode. Outdoor unit does not operate. System operation switches off. System is hard to heat up. System does not heat up instantly. Backup heater is automatically turned ON when it is disabled.
Troubleshooting 10:34am,Mon H76 RC-1 & Indoor communication error Close Reset Below is a list of error codes that may appear on the display when there is some trouble with the system setting or operation. When the display shows an error code as indicated below, contact the number registered in the Remote Controller or a nearest authorised installer. All switches are disabled except and . Error number Blinking Error No.
Information Information when connect to Network Adaptor (Bundled Accessories parts) WARNING Before use, check the safety around the Air-to-Water system. Confirm human and living objects at surrounding before operation. Incorrect operation due to failure to follow instructions may cause harm and damage. Confirm the below before operation (inside premises) - Timer setting condition. Unpredictable on/off operation may cause serious injury or damage to human and living objects.
Information Symbols: Explanation of symbols that may be present in this manual. WARNING 54 This symbol shows that this equipment uses a flammable refrigerant with safety A3 group per ISO 817. If the refrigerant is leaked, together with an external ignition source, there is a possibility of fire / explosion. This symbol shows that the Operation Instructions should be read carefully.
Country Austria Baltic Bulgaria Croatia Czech Republic Denmark Finland France Germany Hotline Phone Number 0800 - 700666 +46 8 680 26 50 +359 2 971 29 69 +36 1 382 60 60 +420 236 032 511 +45 369 277 99 +358 923 195 432 +33(0) 892 183 184 0800 - 2002223 Manufactured by: Panasonic Corporation 1006, Oaza Kadoma, Kadoma City, Osaka 571-8501, Japan Website: http://www.panasonic.