A. CONTROL OVERVIEW
The PUREFIRE
®
boiler control is one of the primary safety
devices for the boiler. It controls the ignition sequence,
temperature limits, circulators and gas flow to the boiler. It
also provides many unique features.
The control provides 8 central heating modes and 3
domestic hot water modes. To provide maximum
flexibility, several special features are also included.
To provide maximum flexibility, several special features
are also included.
1. Central Heating (CH) Modes:
The P
UREFIRE
®
boiler control allows the installer to
choose from several different central heating modes.
The following table shows the central heating modes. In
addition, the table shows the display text associated with
each CH mode and a brief description of the operation.
2. Domestic Hot Water (DHW) Modes:
The P
UREFIRE
®
boiler control also allows the installer
to choose from three different DHW modes.
BOILER CONTROL: INTERNAL WIRING & OPERATION
Table 8.1: Central Heating (CH) Modes
8. BOILER CONTROL: INTERNAL
WIRING & OPERATION
Central Heating Mode Description Restrictions
0 (Indoor Thermostat) Fixed Setpoint Not for space heating
1 (Thermostat and Outdoor Reset) Outdoor Reset No restrictions
2 (Permanent Demand and Outdoor Reset) Outdoor Reset No restrictions
3 (Permanent Demand and Setpoint) Fixed Setpoint Not for space heating
4 (Analog 0-10 VDC Input – Setpoint) Analog Input
External Energy
Management System
5 (Analog 0-10 VDC Input – Modulation Rate) Analog Input
6 (Hydro-Air Unit) Fixed Setpoint Not for space heating
7 (Internal Reset) Default * Internal Reset No restrictions
Table 8.2: Domestic Hot Water (DHW) Modes
Domestic Hot Water Mode Description
0 (No DHW) No DHW tank is used.
1 (DHW Tank with sensor)
The domestic water tank is equipped with a temperature sensor. The PUREFIRE
®
control modulates the boiler
firing rate based on tank temperature
2 (DHW Tank with thermostat)
The domestic water tank is equipped with a thermostat. The PUREFIRE
®
control responds to the demand from
the thermostat and modulates the boiler firing rate targeting the DHW boiler setpoint.