Adjusting the switching points
The ultrasonic sensor features a switch output with two teachable switching points.
These are set by applying the supply voltage -U
B
or +U
B
to the TEACH-IN input. The
supply voltage must be applied to the TEACH-IN input for at least 1 s. LEDs indicate
whether the sensor has recognised the target during the TEACH-IN procedure. Swit-
ching point A1 is taught with -U
B
, A2 with +U
B
.
Five different output functions can be set
1. Window mode, normally-open function
2. Window mode, normally-closed function
3. one switching point, normally-open function
4. one switching point, normally-closed function
5. Detection of object presence
TEACH-IN window mode, normally-open function
Set target to near switching point
TEACH-IN switching point A1 with -U
B
Set target to far switching point
TEACH-IN switching point A2 with +U
B
TEACH-IN window mode, normally-closed function
Set target to near switching point
TEACH-IN switching point A2 with +U
B
Dimensions
Electrical Connection
Pinout
(Torque)
max. 10 Nm
48.4
41
70
LED
17
M12x1
4
6
M12x1
3 (BU)
1 (BN)
2 (WH)
4 (BK)
U
+ U
B
Teach input
Switch output
- U
B
Core colours in accordance with EN 60947-5-2.
Standard symbol/Connections:
(version E5, pnp)
Connector V1
2
3
1
4
Additional Information
Accessories
UB-PROG2
Programming unit
BF 5-30
Mounting flange
BF 12
Mounting flange
BF 12-F
Mounting flange
V1-G-2M-PVC
Cable connector
V1-W-2M-PUR
Cable connector
UVW90-M12
Ultrasonic -deflector
Programmable output modes
1. Window mode, normally open mode
A1 < A2:
2. Window mode, normally closed mode
A2 < A1:
3. One switch point, normally open mode
A1 -> ∞
5. A1 -> , A2 -> : Object presence detection mode
Object detected: Switch output closed
No object detected: Switch output open
4. One switch point, normally closed mode
A2 -> ∞:
object distance
A1
A2
A2
A1
A2
A1