Installation Guide

8
Unconfined Space
A water heater in an unconfined space uses indoor air for
combustion and requires at least 50 cubic feet for each
1,000 BTUH of the total input for all gas appliances. The
table below shows a few examples of the minimum square
footage (area) required for various BTUH inputs.
All Air from Outdoors
Outdoor fresh air can be provided to a confined area either
directly or by the use of vertical and horizontal ducts. The
fresh air can be taken from the outdoors or from crawl or
attic spaces that freely communicate with the outdoors.
Attic or crawl spaces cannot be closed and must be
properly ventilated to the outside.
Ductwork must be of the same cross-sectional area as
the free area of the opening to which they connect. The
IMPORTANT:
The area must be open and be able to provide the
proper air requirements to the water heater. Areas that
are being used for storage or contain large objects may
not be suitable for water heater installation.
Water heaters installed in open spaces in buildings with
unusually tight construction may still require outdoor air
to function properly. In this situation, outside air open-
ings should be sized the same as for a confined space.
Modern home construction usually requires supplying
outside air into the water heater area.
Confined Space
For the correct and proper operation of this water heater,
ample air must be supplied for the combustion, ventilation,
and dilution of flue gases. Small enclosures and confined
areas must have two permanent openings so that sufficient
fresh air can be drawn from outside of the enclosure. One
opening shall be within 12 inches of the top and one within 12
inches of the bottom of the enclosure as shown in Figure 3.
The size of each opening (free area) is determined by the
total BTUH input of all gas utilization equipment (i.e., water
Table 3
BTUH
Input
Min. Sq. Feet
with 8’ Ceiling
Typical Room
with 8’ Ceiling
30,000 188 9 x 21
45,000 281 14 x 20
60,000 375 15 x 25
75,000 469 15 x 31
90,000 563 20 x 28
105,000 657 20 x 33
120,000 750 25 x 30
135,000 844 28 x 30
All Air from Inside the Building
When additional air is to be provided to the confined area
from additional room(s) within the building, the total volume
of the room(s) must be of sufficient size to properly provide
the necessary amount of fresh air to the water heater
and other gas utilization equipment in the area. If you are
unsure that the structure meets this requirement, contact
your local gas utility company or other qualified agency for
a safety inspection.
Each of the two openings shall have a minimum free area
of 1 square inch per 1,000 BTUH of the total input rating of
all gas utilization equipment in the confined area, but not
less than 100 square inches (Figure 4).
heaters, furnaces, clothes dryers, etc.) and the method by
which the air is provided. The BTUH input can be found on
the water heater data plate. Additional air can be provided
by two methods:
1. All air from inside the building.
2. All air from outdoors.
WARNING
Fire and Explosion Hazard
Combustion air is drawn through the
bi-directional air vent above the water
heater.
Do not store gasoline or other flammable
substances above this water heater.
Storage of gasoline or other flammable
substances above this water heater can
result in serious injury or death.
Figure 3
Opening Locations
Confined Spaces
12” Max.
Permanent
openings to
the outside or
additional
rooms within
the building
Closet
or other
confined
space
12” Max.
Figure 4
All Air From Inside Building
Confined Space Installation
Confined
Space
Permanent
Openings
1 Square
inch/1000
BTUH
(min. 100
sq. in.)