User's Guide Power Supply 5115

Installation
4
Powerware
®
5115 User’s Guide www.powerware.com
WARNING
ThisUPScontainsitsownenergy source(batteries).The output receptaclesmay
carrylive voltageeven whenthe UPSisnot connected to an AC supply.
Donot removeor unplugthe inputcord when the UPSisturned on. This removes
the safetyground from theUPSand the equipment connected tothe UPS.
To reduce theriskof fire or electricshock, installthisUPS in atemperature and
humiditycontrolled,indoorenvironment,freeofconductivecontaminants.Ambient
temperaturemustnotexceed40
°C(104°F).Donotoperatenearwaterorexcessive
humidity (95% max).
To complywith internationalstandards,the sumofearth leakagecurrent fromthe
loadconnectedto the UPS must not exceed 1.5 mA.
Installing the UPS
The following steps explain how to install the UPS. Figure 2 shows a
typical installationonly. See “UPS Rear Panels” onpage 6 for the rear
panel of each model.
1. If you are installing power management software, connect your
computer to the UPS communication port using the supplied
communicationcable.
NOTE If you need to change thefactory-set defaults forthe output voltage or input
voltage range,see“Voltage Configuration”on page13 before installing the UPS.
2. On 230V models, plug the power cord into the input connector
on the UPS rear panel.
Customer-supplied power cords must be correctly rated for the
UPS (see “Specifications” on page 23). You can also use the
powercordfromthelargestloadifitiscorrectlyrated.