Specifications
24
Powerware
®
5115 User’s Guide www.powerware.com
Table 5.Electrical Output
120V Models 230V Models
PowerLevels(ratedat
nominalinputs)
500 VA, 320W
750 VA, 500W
1000 VA, 670W
1400 VA, 950W
PowerFactor 500 VA, 0.64
750–1400 VA, 0.67
Regulation(Normalmode) -10% to +6% of nominal voltage
Regulation(Batterymode),
NominalVoltage±5%
Same as selected nominal input voltage
110, 120V
Same as selected nominal input voltage
220, 230, 240V
Voltage Waveform Sinewave
OvercurrentProtection Inverter saturation current limited
OutputReceptacles 500–750 VA: (4) 5-15
1000–1400 VA: (6) 5-15
500–750 VA: (4) 10A, IEC-320
1000–1400 VA: (6) 10A, IEC-320
Table 6.Environmental and Safety
120V Models 230V Models
Operating Temperature Up to 1,500 meters: 0°C to 40°C (32°F to 104°F); UL tested 25°C (77°F)
Above 1,500 meters: 0°C to 35°C (32°F to 95°F)
Transit/Storage
Temperature
-15°C to 55°C (5°F to 131°F)
Relative Humidity 5–95% noncondensing
Operating Altitude Up to 3,000 meters above sea level
Audible Noise Less than 45 dBA typical
SurgeSuppression ANSI C62.41 Category A (formerly IEEE 587)
Safety Conformance UL 1778; UL 497A;
CAN/CSA C22.2, No. 107.1
UL 1778, UL 497A (data line only);
CAN/CSA C22.2, No. 107.1;
EN 50091-1-1 and IEC 60950
Safety Markings UL,cUL UL,cUL,CE,TUV, C-Tick
EMC (ClassB) FCC Part 15, ICES-003 EN 50091-2, FCC Part 15, ICES-003