Use the following procedure to connect utility power and load to the
UPS:
1. Verify that the electrical connections to the installation site have
been properly installed. Compare the circuit breaker ratings and
cable sizes to the ones shown in the terminations table on
page 24.
2. A user-supplied, readily-accessible, disconnection device must
be incorporated in both the input and output wiring (see the
following breaker ratings).
P
o
w
e
r
w
a
r
e
9
1
5
0
Suggested Breaker Ratings
Powerware 9150
Input Output
Model 8 kVA 50A 50A
Model 10 kVA 60A 60A
Model 12.5 kVA 70A 70A
3. Switch off utility power to the distribution point where the UPS
will be connected. Be absolutely sure there is no power.
4. Remove the front panel. Lift from the bottom of the panel and
then pull out (see Figure 5).
5. Remove the left side panel of the UPS by unscrewing the two
screws and pulling the panel (see Figure 5).