User's Guide Power Supply 9150

Installation
29
Powerware
®
9150 User’s Guide www.powerware.com
Powerware 9150 Hardwired Terminations for Optional PDM
WireFunction
Terminal U
p
stream
S
u
g
g
e
s
t
e
d
W
i
r
e
S
i
z
e
*
*
ConduitConnection
Input
T
e
r
m
i
n
a
l
Position*
U
p
s
t
r
e
a
m
CircuitBreaker
Suggested Wire Size**
C
o
n
d
u
i
t
C
o
n
n
e
c
t
i
o
n
(EntrySize)
Ground
TB1-1 8AWG
L1/A TB1-2
70A
4AWG
1-3
/
4 access hole for
L2/B
TB1-3
70A
4AWG
1
-
3
/
4
a
c
c
e
s
s
h
o
l
e
o
r
1-1/4 conduit
Neutral
TB1-4 2AWG
OutputforPDM Wire Color
Ground TB1-6 Green/Yellow
L1/A TB1-7 Black
1-3
/
4 access hole for
L2/B
TB1-8 Red
1
-
3
/
4
a
c
c
e
s
s
h
o
l
e
o
r
1-1/4 conduit
Neutral
TB1-9 White
*All terminal wire size ratings are 8- 4 AWG, except TB1-4 is 8 - 1/0.
**Use 75
C copper wire. Suggested wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16.
NOTE Proper phaserotationmustbe observed.
123 4 678 9
Ground L1/A L2/B N Ground L1/A L2/B N
Input Output
Figure 11. Hardwired Terminal Blocks