UPS Startup on Battery
NOTE Beforeusingthisfeature, theUPSmusthave beenpowered byutility power at
least once so thatthe UPScanauto-detect thefrequency(50 or60 Hz).
1. Remove the front panel. Lift from the bottom of the panel and
then pull out (see Figure 5 on page 22).
2. Verify that the Maintenance Bypass switchis in the UPS
position.
3. Turn the UPS battery breaker CB1 and optional CB2 to the ON
position. If you have additional battery cabinets, turn the circuit
breakers on all battery cabinets to the ON position.
4. Start the UPS by turning on the UPS ON/OFF switch (the
position).
5. Press the Battery Start pushbutton below the UPS control panel
(see Figure 14 on page 39) and hold for approximately five
seconds.
The UPS checks its internal functions and supplies power to the
output. The UPS starts in approximately one minute. The UPS
ON, ON BATTERY, and LOAD indicators illuminate. The
audible alarm sounds; press the RESET pushbutton on the LED
panel to clear the alarm.
6. Reinstall the front panel.