Powerware® Modbus ® Card User’s Guide
Class A EMC Statements FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
Table of Contents 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2 Installing the Modbus Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Inspecting the Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Four-Wire Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TABLE OF CONTENTS ii EATON Powerware® Modbus® Card User’s Guide S 164201376 Rev C www.powerware.
Chapter 1 Introduction The Eaton® Powerware® Modbus® Card is an X-Slot® connectivity device that allows you to continuously and reliably monitor the UPSs in your Building Management System (BMS). The card uses the Modbus protocol to integrate data from the UPS into your building management software, such as WonderwareR.
INTRODUCTION Building Management Software Ethernet Ethernet Gateway RS-485 Network -270.6 -270.6 Power Meter PLC UPS with Modbus Card Figure 2. UPS Integrated with RS-485 Network 2 EATON Powerware® Modbus® Card User’s Guide S 164201376 Rev C www.powerware.
Chapter 2 Installing the Modbus Card The Modbus Card is available: S as a separate card for use with UPSs that have an X-Slot S factory-installed in a Powerware Expansion Chassis Use the following sequence for installing the Modbus Card: 1. For four-wire networks only, change the jumpers on the Modbus Card (see “Four-Wire Communication” on page 4). 2.
INSTALLING THE MODBUS CARD Four-Wire Communication The factory-default setting for the Modbus Card is for two-wire communication. To change the default setting, adjust the jumpers on the Modbus Card. CAUTION To prevent electrostatic discharge (ESD), place one hand on an unpainted metal surface such as the UPS rear panel. 1. If you are installing the Modbus Card into an X-Slot, complete Step 3 only. If you are installing the Powerware Expansion Chassis with your UPS, complete Steps 2 through 4. 2.
INSTALLING THE MODBUS CARD 3. Change the J9 and J10 jumpers to the desired setting as shown in Figure 4. Two-Wire (Default) J10 J7 J8 1 J10 1 J9 J9 1 ON S2 1234 56 Four-Wire J10 J11 1 1 J9 Figure 4. Modbus Card Jumpers 4. Reinstall the Modbus Card into the Powerware Expansion Chassis. Align the Modbus Card with the slot guides and slide the card into the slot until it is firmly seated. Secure the Modbus Card with the screws removed in Step 2.
INSTALLING THE MODBUS CARD Installing the Modbus Card into an X-Slot CAUTION To prevent electrostatic discharge (ESD), place one hand on an unpainted metal surface such as the UPS rear panel. 1. Remove the X-Slot cover (or existing X-Slot module) on the UPS rear panel. Retain the screws (see Figure 5). NOTE Some UPSs may have another X-Slot module already installed (such as the Powerware 9125 UPS).
Chapter 3 Wiring the Modbus Card The Modbus Card provides an easy path for integrating a Powerware UPS into an RS-485 Modbus network and also provides isolation of the communication between the UPS and the RS-485 Modbus network. You can use the DB-9 port or terminal strip on the Modbus Card to wire into a two-wire or four-wire network. Two-Wire Networks The Modbus Card’s default configuration is for two-wire, half-duplex, RS-485 networks.
WIRING THE MODBUS CARD Four-Wire Networks The Modbus Card also supports four-wire, half-duplex, RS-485 networks. Figure 7 shows a detailed view of four-wire connections using the Modbus Card terminal strip. Slave Device #1 Slave Device #2 UPS with Modbus Card TxD+ RxD+ TxD– RxD– R * T Gnd R+ T+ R-- T-- Master Device Gnd R+ T+ R-- T-- R * T R * T T-R-T+ R+ Gnd R * T *See Note Figure 7.
WIRING THE MODBUS CARD For four-wire networks. All four RS-485 network signals including TxD(+), RxD(+), TxD(–), and RxD(–) must be connected to the terminal strip as illustrated in Table 1. Verify that the Modbus Card J9 and J10 jumpers are set to the four-wire option (see “Four-Wire Communication” on page 4). TxD+ RxD+ TxD– RxD– 1 2 3 4 GND 5 Figure 8. RS-485 Terminal Strip Table 1.
WIRING THE MODBUS CARD 5 4 9 3 8 2 7 1 6 Figure 9. RS-485 DB-9 Pin Numbers Table 2. RS-485 DB-9 Pin Assignments Pin Number Modbus Card Signal Name RS-485 Network Signals Master Signal Name 1 RxD(+) TxD(+) 2 TxD(+) RxD(+) 3 Signal common Signal common 4 Reserved — 5 Reserved — 6 RxD(–) TxD(–) 7 TxD(–) RxD(–) 8 Reserved — 9 Reserved — Termination CAUTION Termination resistors should be placed only at the extreme ends of the RS-485 network.
WIRING THE MODBUS CARD Four-Wire Two-Wire ON *Factory-default = OFF *OFF J7 J8 1 2 3 4 5 6 J10 TxD(–) Pull Down (620Ω) J9 TxD(+) Pull Up (620Ω) TxD Terminator (120Ω) 1 S2 J11 RxD Terminator (120Ω) RxD(+) Pull Up (620Ω) RxD(–) Pull Down (620Ω) Figure 10. S2 Termination Configuration If a value other than the on-board 120 ohm termination is required, then S2-3 and S2-4 should be set to the OFF position.
WIRING THE MODBUS CARD RS-232 Modbus Port It is also possible to use the RS-232 Modbus port for connecting to your network. 5 4 9 3 8 2 7 1 6 Figure 11. RS-232 DB-9 Pin Numbers Table 3.
Chapter 4 Modbus Card Configuration The Modbus Card has an RS-232 configuration port that you can access with a terminal or a computer equipped with a terminal emulation program. To use the configuration screens for the Modbus Card, you need: S A serial communication cable (supplied). S A terminal with a serial communication port, or a computer with a terminal emulation program such as HyperTerminalR.
MODBUS CARD CONFIGURATION 2. Press [Enter]. The Configuration screen appears (see Figure 13). Powerware Modbus Card Version 1.00 (1-16-02) Current Configuration: Baud Rate: 9600 Slave Address: 29 ----------------------------------------------------------------------------Valid Commands: AD Change Slave Address, usage AD n, where n is the new slave address for the card (1 - 247 valid). BD Change Modbus Baud Rate, usage BD n, where n is the new baud rate (1200, 2400, 4800, 9600, 19200).
MODBUS CARD CONFIGURATION 4. To configure the slave address, type AD followed by a space and node (1 through 247) and press [Enter]. The default is 29. This setting affects both RS-232 and RS-485 Modbus connections. 5. To save and exit, type SA and press [Enter] to permanently save the new configuration changes. 6. The card is now configured. Shut down the terminal emulation program and disconnect the serial cable from the Modbus Card. 7. Continue to Chapter 5, “Integrating the UPS” on page 17.
MODBUS CARD CONFIGURATION 16 EATON Powerware® Modbus® Card User’s Guide S 164201376 Rev C www.powerware.
Chapter 5 Integrating the UPS Powerware provides a software tool named Modbus Profiler that creates a Modbus register map specifically for your Powerware UPS. Refer to the Master Modbus Register Map for a complete list of the Status, Alarm, and Meter data for all Powerware UPS equipment (open the reg_map.pdf file in the directory where the Modbus Profiler tool is located).
INTEGRATING THE UPS 5. Run profiler from the command prompt or double-click profiler.exe from Microsoft Windows Explorer. By default, Modbus Profiler uses the communication port specified in the [Connection] section of the profiler.ini file. If profiler fails to connect using this communication port, you are prompted with a list of alternate communication ports. You may also edit the Port= value in the [Connection] section of the profiler.ini file to change the default value. 6.
INTEGRATING THE UPS Register Name Value Format Unit 113 Rectifier Input Status 1 BOOL Status 114 Bypass Status 0 BOOL Status 115 Bypass Input Status 1 BOOL Status 116 Input Circuit Breaker Status (CB1) 1 BOOL Status 117 Battery Disconnect Status 1 BOOL Status 118 Inverter Disconnect Status 1 BOOL Status 119 Inverter Status 1 BOOL Status 120 UPM Normal 0 BOOL Status 121 UPM On Battery 0 BOOL Status 122 UPM Bypass (Off Line) 0 BOOL Status 123 UPM Notice
INTEGRATING THE UPS Register 20 Name Value Format Unit 162 Building Alarm 2 1 BOOL Status 163 Building Alarm 1 0 BOOL Status 169 Output overload 0 BOOL Status 172 DC link over voltage 0 BOOL Status 173 DC link under voltage 0 BOOL Status 174 Rectifier failed 0 BOOL Status 176 Battery contactor fail 0 BOOL Status 177 Bypass breaker fail 0 BOOL Status 191 Battery current limit 0 BOOL Status 194 Output current over 100% 0 BOOL Status 199 Shutdown immine
INTEGRATING THE UPS Table 5.
INTEGRATING THE UPS Register 22 Meter Name Scale Unit 62 INVERTER VOLTS PHASE C /10 Volts 66 LOAD CURRENT PHASE A /10 Amps 67 LOAD CURRENT PHASE B /10 Amps 68 LOAD CURRENT PHASE C /10 Amps 69 LOAD CURRENT PHASE A BAR CHART /10 Amps 70 LOAD CURRENT PHASE B BAR CHART /10 Amps 71 LOAD CURRENT PHASE C BAR CHART /10 Amps 72 OUTPUT VA BAR CHART /10 kVA 79 OUTPUT VOLTS A /10 Volts 80 OUTPUT VOLTS B /10 Volts 81 OUTPUT VOLTS C /10 Volts EATON Powerware® Modbus® Card
Chapter 6 Troubleshooting Problem Possible Cause Corrective Action The Modbus Profiler tool does not ggenerate the profiler.csv fil fil file The wrong communication port number was entered in the profiler comX command. Verify the correct port number on your computer that is connected to the Modbus Card. The serial cable is not connected. Verify that the serial cable connections are secure. Communication doesn’t work Incorrect communication parameters.
TROUBLESHOOTING DCE (Default) 1 1 J7 J8 J10 J7 J8 J9 1 ON S2 1234 56 DCE/DTE J11 Two-Wire (Default) J10 1 1 J9 Two-Wire/Four-Wire S2 Termination (Default ”OFF”) J11 Half Duplex (Default) 1 Full-Duplex 1 Figure 15. Modbus Card Default Jumper Settings 24 EATON Powerware® Modbus® Card User’s Guide S 164201376 Rev C www.powerware.
TROUBLESHOOTING Service and Support If you have any questions or problems with the Modbus Card, call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a Modbus Card technical representative.
TROUBLESHOOTING 26 EATON Powerware® Modbus® Card User’s Guide S 164201376 Rev C www.powerware.
*164201376C* 164201376 C