CHAPTER 3
UPS STARTUP
This section provides step-by-step instructions for starting the
Powerware FERRUPS UPS. Follow these procedures closely to avoid
potential damage to your equipment or the UPS and to protect yourself
and others from hazardous operating conditions.
Startup for the FE and QFE 500 VA–3.1 kVA UPS
To start the FE and QFE 500 VA–3.1 kVA UPS, use the following steps:
1. Confirm the equipment to be protected by the UPS is powered
off.
2.
For FE Plug-Receptacle UPSs: Plug the UPS power cord into a
power outlet.
NOTE If the plug does not match your receptacle outlet, ask your electrician to install
the proper outlet.
For QFE Plug-Receptacle UPSs: Disconnect the power cord from
the computer or other equipment to be protected by the UPS
and plug it into the UPS. Plug the other end of the power cord
into a power outlet.
NOTE Do not use the cord supplied with the UPS; this cord is for plugging the
equipment into the UPS output receptacles.
NOTE If the plug does not match your receptacle outlet, ask your electrician to install
the proper outlet.
NOTE If you need to order a UPS power cord, please call your service representative.
For Hardwired UPSs: Confirm that an electrician has completed
and tested the connection to the proper power source and
connected your protected equipment according to the
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation
Guide. Turn the AC line disconnect switch to the ON position.