3.1 kVA/
2.2 kW
2.1 kVA/
1.5 kW
1.8 kVA/
1.25 kW
1.4 kVA/
1kW
1.15 kVA/
800W
850 VA/
600W
700 VA/
500W
500 VA/
350W
Model
Runtime (minutes)
QFE Full Load:
Half Load:
FE Full Load:
9
25
9
14
35
11
11
28
9
18
48
8
14
37
11
11
30
11
9
25
9
14
35
14
Weight :
Without Battery:
60 Hz Models:
50 Hz Models:
With Battery:
60 Hz Models:
50 Hz Models:
44 lb
22.2 kg
54 lb
28 kg
46 lb
25 kg
62 lb
36.3 kg
51 lb
27.7 kg
67 lb
39 kg
92 lb
41.7 kg
102 lb
59.9 kg
106 lb
45.4 kg
122 lb
69.9 kg
120 lb
58.1 kg
176 lb
83 kg
132 kg
63.5 kg
188 lb
89 kg
144 lb
69 kg
248 lb
116.1 kg
Dimensions
(HxWxD)
12x10x 21.25
30.5 x 25.5 x 54.0 cm
15.1x 15.2x 20.2
38.5 x 39.0 x 51.5 cm
21.2x 15.25x 22.9
54.0 x 39.0 x 58.5 cm
1
Size input protection according to all applicable local or national codes. Fuse and circuit breaker sizes vary. Sizes shown
are for the U.S. and Canada.
2
At 0.7 leading power factor.
Table 10. FE and QFE 4.3–18 kVA
Model 4.3 kVA/
3kW
5.3 kVA/
3.7 kW
7kVA/
5kW
10 kVA/
7.5 kW
12.5 kVA/
10 kW
18 kVA/
15 kW
AC Input Voltage and Current, Standard Charger
FE: 120 Vac
208 Vac
220 Vac
240 Vac
QFE: 2
20 Vac
230 Vac
240 Vac
32A
1
18A
17A
16A
19A
18A
17A
38A
1
22A
21A
19A
21A
20A
19A
51A
1
30A
27A
26A
27A
26A
24A
45A
41A
39A
43A
41A
39A
58A
53A
50A
55A
53A
51A
86A
81A
76A
81A
78A
75A
Recommended Input
Service for 60 Hz
Models
2
120 = 40A
1
208 = 25A
240 = 20A
120 = 50A
1
208 = 30A
240 = 25A
120 = 65A
1
208 = 40A
240 = 35A
208 = 60A
240 = 50A
208 = 75A
240 = 65A
208 = 115A
240 = 100A