User Guide

Troubleshooting
62
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com
What To DoWhat It MeansAlarm
Message
Audio
Code
Letter
T Call
Service
The UPS has detected a problem that
requires service.
The UPS shuts down. Contact your service
representative.
W : –– Fan Alarm The fan has stopped. The UPS may have shut down; if so,
contact your service representative. If the
UPS has not shut down, shut down your
equipment or bypass the UPS; then, turn
the UPS off and contact your service
representative.
Alarm and Inverter Logs
Your FERRUPS UPS makes an entry in its logs every time it sounds an
alarm or switches to inverter (battery power). This information can be
helpful in diagnosing problems.
You can view the Alarm and Inverter Logs from either the UPS control
panel or a terminal or computer that you have connected to the RS-232
port (see “Connecting a Terminal or Computer to the RS-232 Port” on
page 41).
Reading the Alarm Log from a Control Panel
The Alarm Log is parameter 25. To display the Alarm Log from a control
panel, follow these steps:
Press this key: Display shows:
[DISPLAY]
'LVSOD\
[2][5] 'LVSOD\ 
[ENTER]  $ODUP /RJ
The display scrolls through the 20 most recent entries in the Alarm Log.
If you have not had 20 alarm conditions, the display scrolls through the
entries FERRUPS has recorded. You can use the number keys as you
view this scrolling display:
Use this key: To do this:
[0] Pause the scrolling and start it again.
[1] through [9] Go to the next log entry.