Specification Sheet

Web: www.prescolite.com
Tech Support: (888) 777-4832
701 Millennium Blvd. Greenville, SC 29607 U.S.A.
Phone (864) 678-1000
Copyright ©2011 Prescolite, Inc., a division of Hubbell Lighting, Inc. All Rights Reserved
Specifications subject to change without notice. Printed in U.S.A. LFR-CFL-016 9/6/11
PHOTOMETRIC DATA
LiteFrame
®
- 6" Vertical Triple Tube
Open Downlight - LF6CFV
LUMINANCE DATA IN CANDELA/Sq. METER
Angle in Average
Vertical
45° 30812
55° 20813
65° 5367
75° 461
85° 0
NOTES
Refer to www.prescolite.com for additional photometric tests
(IES Files).
When ordering a sloped ceiling adapter, specify the degree
of slope in 5° increments, max. of 35°. For a more precise
degree or wet ceiling applications, please contact factory.
Sloped ceiling adapter and housing must be installed at the
same time prior to finish ceiling installation.
26W Triple 32W Triple 42W Triple
120V 277V 347V 120V 277V 347V 120V 277V 347V
Total System Watts 29 29 31 36 36 36 46 46 50
Input Current (Amps) 0.24 0.11 0.09 0.31 0.13 0.11 0.38 0.17 0.15
Input Frequency in Hz 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60
Power Factor <.98 <.98 <.95 <.98 <.98 <.95 <.98 <.98 <.95
Ballast Factor <1.1 <1.1 <1.02 <.98 <.98 <.98 <.98 <.98 <1.0
Total Harmonic Distortion <10% <10% <10% <10% <10% <10% <10% <10% <10%
BALLAST DATA
Rated W tts 26W T iple 32W Triple 42W Triple
Rated Lumens 1710 2200 3200
Efficacy (LPW) 66 69 76
Rated Life 12,000 12,000 12,000
CRI 82 82 82
Min. S arting Temp. 32°F 32°F 32°F
LAMP DATA CFLH1/CFLV
LF6CFV32EB/6CFV with Clear Alzak Reflector
Lamp: 1-CF32DT/E/IN/830-SYLVANIA
Spacing Criteria: 1.4
Efficiency: 55.9%
Test No. ITL60612
CANDLEPOWER
DISTRIBUTION
07
/
CFV
PEN HO
PACT FLUORE CENT SYLV
A
P
DEPE NDENT T ORATOR IES N
8 NG U DE , A
l@ i l d TE
d
N HITE
Angle
0 505
5 530
10 553
15 569
20 586
25 597
30 595
35 547
40 461
45 365
50 281
55 200
60 126
65 38
70 3
75 2
80 1
85 0
90 0
CANDLEPOWER
SUMMARY
LF6CFV32EB/6CFV
Test No. ITL60612
% Effective Ceiling Cavity Reflectance
80% 70% 50% 30% 10%
20% Effective Floor Cavity Reflectance
% Wall Reflectance
70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10
1 .62 .60 .59 .57 .61 .59 .58 .56 .57 .56 .54 .55 .54 .53 .53 .52 .51
2 .58 .54 .51 .49 .57 .53 .51 .48 .51 .49 .47 .50 .48 .46 .48 .47 .45
3 .54 .49 .45 .42 .52 .48 .45 .42 .46 .44 .41 .45 .43 .40 .44 .42 .40
4 .50 .44 .40 .37 .49 .43 .39 .37 .42 .39 .36 .41 .38 .36 .40 .37 .35
5 .46 .40 .35 .32 .45 .39 .35 .32 .38 .35 .32 .37 .34 .31 .36 .33 .31
6 .43 .36 .32 .29 .42 .36 .31 .28 .35 .31 .28 .34 .31 .28 .33 .30 .28
7 .40 .33 .29 .25 .39 .33 .28 .25 .32 .28 .25 .31 .28 .25 .30 .27 .25
8 .37 .30 .26 .23 .36 .30 .26 .23 .29 .25 .23 .28 .25 .23 .28 .25 .22
9 .35 .28 .24 .21 .34 .27 .23 .21 .27 .23 .21 .26 .23 .20 .26 .23 .20
10 .33 .26 .22 .19 .32 .25 .21 .19 .25 .21 .19 .24 .21 .19 .24 .21 .19
Room Cavity
Ratio
COEFFICIENTS OF UTILIZATION Zonal Cavity Method
AVERAGE INITIAL FOOTCANDLES ON WORKPLANE
Assumptions:
1. Ceiling 80% Wall 50% Floor 20%
2. 4 Luminaires evenly spaced in the center of the room.
3. The room is square and has a width and length equal to twice the
lamp spacing (LS).
4. RCR is Room Cavity Ratio.
5. Dirt and Lumen Depreciation Factors are 1.0.
6. Ballast Factor is 1.0 for ballasted fixtures.
LS (Feet) (Footcandles)
RCR1 RCR3 RCR7
7.0 29 24 16
8.0 23 18 12
9.0 18 15 10
10.0 14 12 8
11.0 12 10 7
12.0 10 8 6
13.0 9 7 5
14.0 7 6 4
15.0 6 5 4
Test No. ITL60612
90º
75º
60º
45º
15º
30º
190
380
570
Test No. ITL60612