OPERATIONS for E5CN (Continued):
Using the keys:
This section describes the basic functions of the front panel keys.
Level Key: Press this key to move between setting levels. The setting level is
selected in the following order: operation level: adjustment level, initial setting
level, communications setting level.
Mode Key: Press this key to change parameters within a setting level. The
parameters can be reversed by holding down the key (moving one per second in
reverse order).
Up Key: Each press of this key increments the value displayed on the No. 2
display or
advances the setting. Holding the key down speeds up the incrementation.
Down Key: Each press of this key decrements values displayed on the No. 2
display or reverses the setting. Holding the key down speeds up the
incrementation.
Selecting Menu Levels:
The following section describes how to access the various menu levels in the Omron
controller.
Operations Level: Press the mode key.
Adjustment Level:
Press and hold the level key for at least 1 second.
Initial Setting Level:
Press and hold the level key for at least 3 seconds.
Protect Level:
Press and hold the level key and the mode key
simultaneously for at least 3 seconds.
Advanced Function Setting Level:
(Note: in order to access this level, the ICPt setting
in the protect level must be set at 0) Index through the
initial setting level and adjust the AmoV setting to “-169”.
M-45-02 TYTAN Manual
Revision - Date: 01 – 11/16/07
28