Instruction manual

OPERATIONS for E5CN (Continued):
Mode Parameter Settings:
The Omron E5CN temperature controller has been programmed prior to shipment, so
no additional programming is normally necessary. The table below shows the various
controller settings for this unit when properly configured to operate the TYTAN inline
heater. Some internal menus have been factory programmed and subsequently locked.
Those menus are not listed.
The selections in bold indicate settings that have been changed from the original
factory default for operation with the TYTAN inline heater.
Level Parameter
Description Setting
R-S Run – Stop selection RUN
AL-1 Alarm value 1 120°C
Operations
Level
AL-2 Alarm value 2 110°C
LAdJ Adjustment level
At Autotune execute OFF
INS Temperature input shift 0.0
P Proportion band 80**
I Integral time 233**
D Derived time 40**
SPRt SP ramp set value OFF
OL-H MV upper limit 100.0
Adjustment
Level
OL-L MV lower limit 0.0
** The P, I and D values may change following the execution of Auto-tune.
Table 6: Omron E5CN Parameters
M-45-02 TYTAN Manual
Revision - Date: 01 – 11/16/07
29