OPERATIONS for E5CN (Continued):
Changing Primary Set Point:
The process Set Point can be changed in the normal display mode. 1.
2. Press the up and down arrow keys to select the desired setting.
After changing the process set point (SP-0) on the Omron controller, you must
manually adjust the SP2 setting on the Future Design over-temperature control.
See OPERATIONS Over-Temperature Controller FDC-L91 section.
High Alarm:
The Omron E5CN temperature controller incorporates an independent high-temperature
alarm. Alarm 1 (AL-1) prevents heater operation above a preset maximum temperature
that may harm the process and potentially the tank material. If the process temperature
exceeds the preset high alarm value, the heater will be disengaged and the audibly
alarm will sound. The temperature controller will activate once the process temperature
exceeds the set point by the preset value. The factory setting of this alarm temperature
is 248°F (120°C).
The high alarm value can be adjusted to a lower setting through the operations level.
Press the mode key to enter the operations level. 1.
Press the mode key to index through the operations level to the AL-1 setting. 2.
Press the up or down key to adjust AL-1 to the desired setting. 3.
4. Press the mode key to index through the operations level to the AL-2 setting.
The AL-2 setting is normally set at 10°C below AL-1. Press the up and down keys to
adjust AL-2 to the desired setting.
5.
6. Press and hold the level key for a minimum of three seconds to return to the normal
display.