Instruction manual

OPERATIONS (Continued):
Mode Parameter Settings:
The Futuredesign FDC-L91 temperature controller has been programmed prior to
shipment, so no programming will be necessary. The table below shows the various
controller settings for this unit when properly configured to operate the TYTAN inline
heater.
Parameter
Description Default Setting
HSP1 Hi Limit Set Point 120 C / 248 F
LSP1 Low Limit Set Point 82 C / 180 F
SP2 Set Point 2 value, for Output 2 10 C / 18 F above”SP0” of the
E5CN Temperature Controller
INPT Input Type Selection J_tC
UNIT Process Unit C / F
RESO Display Resolution NodP
IN.LO Low Scale for Linear Input 0
IN.HI High Scale for Linear Input 100 C / 212 F
SHlF PV Shift (offset) Value 0
FILT PV Filter Time Constant 2
OUT1 Output 1 Function HI
O1.HY Output Hysteresis Value 0.1
HSP.L Lower Limit of HSP1 0
HSP.H Upper Limit of HSP1 150 C / 302 F
LSP.L Lower Limit of LSP1 0
LSP.H Upper Limit of LSP1 120 C / 248 F
OUT2 Output 2 Function ALA
ADDR Address Assgnmnt of Digital Com Not used
BAUD Baud Rate of Digital Com Not Used
PARI Parity Bit of Digital Com Not Used
AL.FN Alarm Function PYLA
AL.MD Alarm Mode Norm
AL.HY Alarm Hysteresis 0.1
AL.FT Alarm Failure Transfer ON
EIFN Event Input Function 0
DISP Normal Display Format PV
Table 8: Future Design L91 Parameters
M-45-02 TYTAN Manual
Revision - Date: 01 – 11/16/07
40