MICRO GROW GREENHOUSE SYSTEMS, INC 26111 YNEZ RD., SUITE C-4, TEMECULA, CA 92591 PHONE (909)-296-3340 FAX (909)-296-3350 Revision 1.
INSTALLATION PROCEDURES GROWMASTER SERIES OF CONTROLLERS PANEL MOUNTING Mount the control panel in an accessible location. Make sure that the location is free of vibration and in close proximity to the devices being controlled. Always consider voltage drop of electrical current when locating the control panel. Securely mount the panel. SWITCHING CONTACTORS AND RELAYS The control panel will operate the greenhouse equipment via load contactors and load relays.
WIRING METHODS Always use stranded wire when connecting cables or conductors to the actual circuit board of the control panel. This will allow flexibility. Use no smaller than #18 gauge stranded wire for all outputs. Use no smaller than the recommended wire size of stranded cable for inputs, generally #22 gauge. SENSOR CONDUCTORS: Route sensor conductors separately from control conductors. This is very important so as to reduce electrical interference.
GROWMASTER PROCOM OPERATING INSTRUCTIONS PROCOM SERIES The PROCOM Series is a completely programmable greenhouse computer system. Any output may be assigned to any input or function. The PROCOM is set up by Micro Grow Greenhouse Systems, Inc. and preprogrammed for the individual requirements of the control system in use. PROGRAMMING LIGHTS RUN - Indicates that the system is in the running mode. SET PROGRAM-All temperatures, humidity levels, and other information are set here.
PROGRAMMING SWITCHES There are three main programming switches located on the Growmaster front panel. These are: RUN-SET SWITCH RUN-Puts the control in the RUN mode. SET-Puts the control in the SET mode in order to set all functions as outlined on the programming lights. PRIOR-NEXT SWITCH PRIOR-Advances to the prior item in the menu. NEXT-Advances to the next item in the menu. VALUE UP-VALUE DOWN SWITCH VALUE UP-Increases the value in the display. VALUE DOWN-Decreases the value in the display.
RUN REPORTS The RUN REPORTS mode allows the grower to run selected reports on the sensor history. 1. Enter the RUN REPORTS mode. 2. Use the PRIOR-NEXT switch to advance to the desired report. 3. Continue to use the PRIOR-NEXT switch to advance and view reports. Display Report (Inside) Select the desired report for display. CALIBRATE The CALIBRATE mode is used in order to calibrate all of the sensor readings.
GROWMASTER PROCOM SET UP SET SYSTEM The SET SYSTEM mode is used to set the system clock and date, manually view the system's sunrise and sunset times, adjust the system photocell, and to set the custom identification that will appear on the display during the run mode. Also, this mode is used to determine the times of day, either by sunrise, sunset, clock, or a combination of means, by which the four separate settings will apply. The four settings are listed as DAY, MIDDAY, EVENING, and NIGHT.
Remote ID Code: (0) Not applicable if not using the GROWLINK program. Set the ID code here for the Growlink remote PC program available from Micro Grow Greenhouse Systems Inc. Every ID code must be different for each Procom. Link Air 1 To Output (1) Select the output that the Air Circulation output will be linked to. You may select any stage of operation; even a vent or shade position may be selected.
SET COOLING The SET COOLING mode will be used to set the desired cooling stage temperature separations and differentials. The internal time delays that will prevent rapid cycling are also set here. Also, this mode is used to determine if any of the cooling stages will be activated during the dehumidify functions of the system. You may choose either the immediate dehumidify function, or the delayed dehumidify function.
The Solar Adjustment feature allows the grower to adjust the cooling temperature setpoint up or down depending on how intense the solar level is. The solar level is monitore4d by the K-Lux sensor if used. The solar level can also be monitored by a PAR or Pyranometer sensor if connected to the Procom. Setpoint Ramp (30) Minutes/Deg This is the ramp time of the heating system. Enter the desired time that it will take the system to implement a change in the heating setting.
SET HEATING The SET HEATING mode will be used to set the desired Heating stage temperature separations and differentials. The internal time delays that will prevent rapid cycling are also set here. Also, this mode is used to determine if any of the Heating stages will be activated during the dehumidify functions of the system. You may choose either the immediate dehumidify function, or the delayed dehumidify function.
The Solar Adjustment feature allows the grower to adjust the cooling temperature setpoint up or down depending on how intense the solar level is. The solar level is monitore4d by the K-Lux sensor if used. The solar level can also be monitored by a PAR or Pyranometer sensor if connected to the Procom. Setpoint Ramp (30) Minutes/Deg This is the ramp time of the heating system. Enter the desired time that it will take the system to implement a change in the heating setting.
SET VENTILATION The SET VENTILATION mode is used to set the number of desired stages of the vent openings, the desired position of each stage, the actual total opening time for the vent itself, and to let the system know if there is a safety time delay in the vent control panel being used. The programming also allows the vent to be linked to a cooling stage or to override input if desired. The dehumidify functions of the vent, both immediate and timed, are programmed here.
Link Vent 1 to Override Inp (NO) Use this setting if any override inputs are in use. Override inputs can come from the use of a Weather Station, or other external device. Mx Vent Pos on Override 1 (CL) If a link is made to override input, the system will then ask what the maximum vent position should be during that override input period. Vent 1 Stg (1) On Immed Dehum Vent 1 Stg (1) On Delay Dehum Set the desired stages of operation here that will be activated by the dehumidify functions.
SET SHADING The SET SHADING mode will determine the total number of shade opening stages, the system timing for the shade system, the solar level differential, and a maximum closed position for the shade system. The actual total opening time for the shade system itself is entered here, and information as to a safety delay that may be present in the actual shade control panel being used is also entered here. The heat retention feature of the shade system can be programmed in this mode.
Go to (0) % if (Mode) = (Eve) Enter the percent of the close position that you want the shade system to go to during heat retention. Also, select the mode of operation desired to initiate the heating retention program. And (Air Temp 1) >= 80 Select the sensor, and the setting to be used (if any) to also activate the shade system for heat retention. You may also choose to ignore any sensors if you like.
SET FOGGING The SET FOGGING mode is used to set the temperature and humidity differentials and the system timing for the fogging output. The grower can also select if the fogging system should be maintained on or pulsed in this mode. 1. Enter the SET FOGGING mode. 2. Use the PRIOR-NEXT switch to advance to the desired item to set. 3. Use the VALUE switch to toggle between desired choices that the system has internally provided. Fog 1 Diff.
SET HEAT VALVES The SET HEAT VALVES mode is used to set the criteria for any modulating heat valves in use. In the event that hot water valves are in use, the total opening time is set here. In addition, the run and wait times for the valves, the hot water differential, and the minimum and maximum hot water temperatures are entered here. If a reference temperature is being used to control the hot water temperature, the minimum and maximum reference temperatures are also entered here.
Reference Temp: (Air Temp 1) Set the desired input to be used as the reference temperature or NONE if no reference temperature is desired. If CO2 Active o Min Wtr 120 F If you are using the CO2 program, the hot water valve may be driven open by entering a separate hot water temperature here. If CO2 is not in use, disregard this feature. Activate on Dehum? (Y) If you would like to activate the hot water valve when the dehumidify program is in use, please enter that here.
PULSED HEATING VALVES Use The Below Settings Only if You are Using a “Pulsed Heat Valve” The Pulsed Heat Valve is Different Than a “Hot Water Valve” Open Heating 2 In (4) Positions Set the desired number of heating stages here. The system can operate the proportional valve in up to eight separate stages. Heating 2 Pos 1 10% Open Set the desired percentages of opening here for each stage. The final stage will always be set to 100%.
SET DEHUMIDIFY The SET DEHUMIDIFY mode is used to enable or to disable the dehumidify functions of the control. The run time of the immediate and the delayed dehumidify functions are set here. The repeat time of the dehumidify feature is set here. The dehumidify differential, and the maximum heat loss and gain for the dehumidify mode are also entered here. 1. Enter the SET DEHUMIDIFY mode. 2. Use the PRIOR-NEXT switch to advance to the desired item to set. 3.
SET CROP LIGHTING The SET CROP LIGHT mode allows the grower to set time delays, solar levels, and other criteria for the crop lighting outputs. 1. Enter the SET CROP LIGHT mode. 2. Use the PRIOR-NEXT switch to advance to the desired item to set. 3. Use the VALUE switch to toggle between desired choices that the system has internally provided. Crop Lgt 1 (ON at All Levels) Set the desired light level at which the crop lighting output should energized. If light level is not a factor, select ON at All Levels.
SET CO 2 2 2 2 All the desired CO settings will be made in the SET CO mode. Linking of CO to a Ventilation or Cooling output, setting of differentials, and time delays. 2 1. Enter the SET CO mode. 2. Use the PRIOR-NEXT switch to advance to the desired item to set. 3. Use the VALUE switch to toggle between desired choices that the system has internally provided, or to increase or decrease the desired display setting.
SET ALARM All of the desired alarm settings will be made in the SET ALARM mode. Set the high and low alarm settings for the individual sensors. 1. Enter the SET ALARM mode. 2. Use the PRIOR-NEXT switch to advance to the desired item to set. 3. Use the VALUE switch to toggle between desired choices that the system has internally provided, or to increase or decrease the desired display setting.
OUTPUT #1 OUTPUT #2 OUTPUT #3 OUTPUT #4 OUTPUT #5 OUTPUT #6 OUTPUT #7 OUTPUT #8 OUTPUT #9 OUTPUT #10 OUTPUT #11 OUTPUT #12 24 VAC POW ER INPUT 24 VAC POW ER INPUT FUSED 24 VAC ALARM SENSOR RS 485 1 2 3 4 DIGITAL IN PUTS SENSOR INPUT TERM IN AL STRIP POW ER IN PUT AND CONTROL OUTPUT STRIP 1 2 3 4 5 6 7 8 9 10 11 12 COM AC IN FUSED AC 1 2 3 4 TRANSFORM ER NOTE: USE A M ACHINE TOOL VARIETY ONLY. 100 VA IS RECOM M ENDED.IF A SM ALLER SIZED TRANSFORM ER IS USED,ADJUST THE FUSE PROTECTION ACCORDINGLY.
FUSED 24 VAC 24 VAC COM OUTPUT #13 OUTPUT #14 OUTPUT #15 OUTPUT #16 OUTPUT #17 OUTPUT #18 CONTROL OUTPUT STRIPS 1 2 3 4 5 6 CONTROL OUTPUT STRIPS 1 2 3 4 5 6 RIBBON CABLE OUTPUT NOTE: THE CONTROL OUTPUTS ARE RATED AT 1 AM P EACH M AXIM UM .DO NOT EXECEED THIS OR DAM AGE M AY RESULT.DO NOT EXCEED 1 AM P FOR ANY SINGLE OUTPUT OR 4 AM PS TOTAL FOR ALL OUTPUTS.
+5VDC SENSOR COMMON SENSOR COMMON 1 2 3 4 5 6 SEN SOR IN PUT TERM IN AL STRIP 7 8 GROW M ASTER PROCOM IN PUTS COM COM +5VDC 1 2 3 4 5 6 7 8 SEN SOR M IC RO G RO W G REENHO USE SYSTEM S,INC . 26111 Ynez Road,Suite C -4 Tem ecula,C A 92591 Phone 909.296.3340 Fax 909.296.3350 SEE IN D IVID UAL SEN SOR D RAW IN GS FOR D ETAILED CON N ECTION S.
VIO RAIN H EATER W IN D D IRECTION GRY FUSED 24 VAC BLU W HT +5 VD C OUTD OOR TEM P. RED YEL W IN D SPEED BLK RAIN GRN W IN D SPEED RAIN N ORTH W IN D D IRECTION BLUE OVERRID E 1 OVERRID E 2 OVERRID E 3 24 VAC COM M ON SECURELY M OUN T TH E OUTD OOR SEN SOR AT TH E H IGH EST UN OBSTRUCTED POIN T ON TH E GREEN H OUSE.
SEN SOR IN PUTS OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT #1 #2 #3 #4 #5 #6 #7 #8 #9 #10 #11 #12 4 3 2 1 D IGITAL OVERRID E INPUT TERM IN AL STRIP GREEN W H ITE BLACK RED OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT SEN SOR IN PUTS 1 2 3 4 5 6 7 8 9 10 11 12 COM AC IN FUSED AC 1 2 3 4 #1 #2 #3 #4 #5 #6 #7 #8 #9 #10 #11 #12 4 3 2 1 GROW M ASTER 2 GREEN W H ITE BLACK RED D IGITAL OVERRID E INPUT TERM IN AL STRIP 2 -
OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT SEN SOR IN PUTS 1 2 3 4 5 6 7 8 9 10 11 12 COM AC IN FU SED AC 1 2 3 4 #1 #2 #3 #4 #5 #6 #7 #8 #9 #10 #11 #12 4 3 2 1 D IGITAL OVERRID E IN PUT ST RIP GROW M ASTER 1 GROW LIN K CON VERTOR BOX *** ALL SH IELD S TOGETH ER, BUT D O N OT LAN D ON BOARD .
SEN SOR COM M ON TEM PERATURE BLACK RED AIR TEM PERATURE OR OUTD OOR TEM PERATURE SEN SOR TO SENSOR TERM IN AL STRIP GREEN RED W HITE BLACK TO SENSOR TERM INAL STRIP W H ITE BLACK KLUX SEN SOR KLUX SEN SOR RED SEN SOR COM M ON +5VD C 24 VAC COM M ON 24 VAC POW ER SENSOR COM M ON +5 VDC AIR TEM PERATURE HUM IDITY W HITE BLUE GREEN RED ORANGE OR BROW N BLACK ASPIRATED AIR TEM PERATURE AN D H UM ID ITY SEN SOR FROM TRAN SFORM ER ROUTE TO SEN SOR IN PUT TERM INALS LOCATE SENSOR IN THE CENTER OF TH
TO SEN SOR TERM IN AL STRIP BLACK RED BLACK RED SOIL TEM PERATURE SEN SOR SEN SOR COM M ON TEM PERATURE +5 VD C SOIL TEM P. PROBE ATTACH USIN G M ETAL PIPE CLAM P 31 SEN SOR COM M ON SOIL TEM PERATURE TO SEN SOR TERM IN AL STRIP 2.8K OH M S 1% AVAILABLE FROM M ICRO GROW H OT W ATER PIPE TEM PERATURE SEN SOR PROCOM SEN SORS Drawn by PRO C O M HO T W ATER & SO IL TEM P SENSO RS Date Distributor O rderID GH 11/29/01 N/A N/A 26111 Ynez Road,Suite C -4 Tem ecula,C A 92591 Phone 909.296.
M OUNTING PLATE SENSOR CONNECTIONS TO CONTROL DISPLAY ENG ELHARD 8 7 6 5 4 3 2 1 ENG ELHARD 2 1 C02 SENSOR INCREASE/DECREASE SELECTION VALUE **FOR EXTERNAL CONNECTION OF ALARM CONTACTS **ALARM RELAY NOTE: RELAY CONTACTS 1 Amp M AX. ALARM SET TO 1000 PPM . SEE M ANUFACTURER'S INSTRUCTIONS TO CHANGE FACTORY SETTINGS.
ROUTE TO PROCOM INPUTS SENSOR COM M ON PYRA SENSOR +5 VDC JUM PER POSITION (LI-200 SZ) CUT OUT PULLUP RESISTOR FOR PYRANOM ETER INPUT ON GROW M ASTER PROCOM . GND SIG OUT +5 VDC RED BLACK (COAXIAL CABLE) SHIELD SIGNAL OUT JUM PER POSITION (+5VDC OUTPUT) (2 CON DUCTOR CABLE) LI-COR PYRANOM ETER 33 SENSOR CONNECTIONS TO PROCOM CONTROL W HITE BLACK RED SHLD/GND SIG IN EM E SYSTEM S AM PLIFIER PCB NOTE:LOCATE AM PLIFIER CIRCUIT BOARD W ITHIN PROCOM ENCLOSURE.SECURELY M OUNT TO BACK OF ENCLOSURE.
ROUTE TO PROCOM IN PUTS SEN SOR COM M ON PAR SENSOR +5 VDC JUM PER POSITION (LI-190 SZ) CUT OUT PULLUP RESISTOR FOR PYRAN OM ETER IN PUT ON GROW M ASTER PROCOM . GN D SIG OUT +5 VD C RED BLACK (COAXIAL CABLE) SH IELD SIGN AL OUT JUM PER POSITION (+5VD C OUTPUT) (2 CON D UCTOR CABLE) LI-COR PAR SEN SOR 34 SEN SOR CON N ECTION S TO PROCOM CONTROL W HITE BLACK RED SH LD /GND SIG IN EM E SYSTEM S AM PLIFIER PCB N OTE: LOCATE AM PLIFIER CIRCUIT BOARD W ITH IN PROCOM EN CLOSURE.
OVERRID E 1 USE TH E SAM E CON FIGURATION FOR OVERRID ES 2, 3 AN D 4. OVERRID E 4 CAN ALSO BE USED AS PH OTOCELL IN PUT.
T2 L2 T1 L1 8 4 14 12 5 1 13 9 C O NTAC TO R NO TES: LINES O N L3,L2,L1 LO ADS O N T3,T2,T1 RELAY NO TES: RELAYS ARE DPDT 14,13 .....24 VAC CO IL 12,9 .....C O M M O N TERM INALS 8,5 .....NO RM ALLY O PEN TERM INALS .....NO RM ALLY CLO SE TERM INALS 4,1 36 T3 L3 SURG E PRO TEC TIO N DEVICE RATED FO R 24 VAC O PERATIO N.
TO OUTPUT TO TURN ON D EVICE TO TRAN SFORM ER (COM M ON SID E) LOAD #3 LOAD #2 LOAD #1 CIRCUIT #1 CIRCUIT #2 CIRCUIT #3 TO M OTOR TO LOAD CEN TER 37 T3 T2 T1 L3 L2 L1 COIL SURGE PROTECTION D EVICE RATED FOR 24 VAC OPERATION . PROVID ED W ITH EACH UN IT CON N ECTION OF LOAD S TO A LOAD CON TACTOR.
H IGH -SPEED FAN LOW -SPEED FAN ROUTE TO 24 VAC COM M ON ELECTRICAL IN TERLOCK 8 N .O. 4 N .C. 5 N .O. 1 N .C.
LIMITED WARRANTY Micro Grow Greenhouse Systems, Inc. warrants that all of the products Micro Grow Greenhouse Systems, Inc. manufactures are free from defects at the time of shipment by Micro Grow Greenhouse Systems, Inc. This warranty covers defects in workmanship and materials. No warranty is extended on any parts, materials, or components manufactured by others and purchased by Micro Grow Greenhouse Systems, Inc.