Operating instructions

13
Link Vent 1 to
Override Inp (NO)
Use this setting if any override inputs are in use. Override inputs can come from the use of a Weather Station, or
other external device.
Mx Vent Pos
on Override 1 (CL)
If a link is made to override input, the system will then ask what the maximum vent position should be during that
override input period.
Vent 1 Stg (1)
On Immed Dehum
Vent 1 Stg (1)
On Delay Dehum
Set the desired stages of operation here that will be activated by the dehumidify functions. You may choose either
the IMMEDIATE or the DELAYED dehumidify functions, or both, for a particular stage. This setup is not applicable
to “PAD VENT”.
Vent 1 Stages
(2
o
Sep.) 2
o
Dif.
Set the desired separation of the ventilation stages here, and also the desired differential. The separation is the
total number of degrees that separate each stage of operation. Once an output or a stage has been activated the
differential is the amount of temperature change required that the will cancel the operation of that stage or output.
This setup is not applicable to “PAD VENT”.
Vent 1 Timing
(2 Sec.)
Set the desired time delay here. The time delay will be active on both energizing and de-energizing stages. This
setup is not applicable to “PAD VENT”.
Reference Temp:
(Sensor Selection)
(IF USED)
Min Ref (0
o
)
Go To (0%) Normal
Max Ref (70
o
)
Go To (100%) Normal
Use this selection to enter a reference temperature for the vent system. For example, select the outdoor sensor,
then enter a minimum and maximum reference temperature, and a minimum and maximum ventilation position.
The Procom will then constantly adjust the ventilation position based on the outdoor temperature.