Operating instructions

19
PULSED HEATING VALVES
Use The Below Settings Only if You are Using a “Pulsed Heat Valve” The Pulsed Heat
Valve is Different Than a “Hot Water Valve”
Open Heating 2
In (4) Positions
Set the desired number of heating stages here. The system can operate the proportional valve in up to eight
separate stages.
Heating 2 Pos 1
10% Open
Set the desired percentages of opening here for each stage. The final stage will always be set to 100%.
Opening Time
Heating 2 3:00
Set the actual time that the valve takes to run from its fully closed position to fully open. This time is critical, as the
system will use this to determine correct openings.
Heating 2 Stg (1)
On Immed Dehum
Set the desired stages of operation here that will be activated by the dehumidify functions. You may choose either
the IMMEDIATE or the DELAYED dehumidify functions, or both for a particular stage.
Heating 2 Stages
(2
o
Sep.) 2
o
Dif.
Set the desired separation of the heat valve stages here, and also the desired differential. The separation is the
total number of degrees that separate each stage of operation. Once an output or a stage has been activated the
differential is the amount of temperature change required that will cancel the operation of that stage or output.
Heating 2 Timing
(2 Sec.)
Set the desired time delay here. The time delay will be active on both energizing and de-energizing stages.