Operating instructions

8
SET COOLING
The SET COOLING mode will be used to set the desired cooling stage temperature separations and differentials.
The internal time delays that will prevent rapid cycling are also set here. Also, this mode is used to determine if
any of the cooling stages will be activated during the dehumidify functions of the system. You may choose either
the immediate dehumidify function, or the delayed dehumidify function. You may adjust the cooling temperatures
throughout the day based on the intensity of the solar level. You also can link any cooling selection to another
output in order to completely or partially disable that set of cooling when the other output, including a vent or a
shade system, is active. The temperature ramping time can be entered here. This is the amount of time required
to change the temperature from one mode to the next.
1. Enter the SET COOLING mode.
2. Use the PRIOR-NEXT switch to advance to the desired item to set.
3. Use the VALUE switch to toggle between desired choices that the system has internally provided.
Cooling 1 Stages
(2
o
Sep.) 2
o
Dif.
Set the desired separation of the cooling stages here, and also the desired differential. The separation is the total
number of degrees that separate each stage of operation. Once an output or a stage has been activated, the
differential is the amount of temperature change required that will cancel the operation of that stage or output.
Cooling 1 Timing
(2 Sec.)
Set the desired time delay here. The time delay will be active on both energizing and de-energizing stages.
Cooling 1 Stg (1)
On Immed Dehum
Cooling 1 Stg (1)
On Delay Dehum
Set the desired stages of operation here that will be activated by the dehumidify functions. You may choose either
the IMMEDIATE or the DELAYED dehumidify functions for a particular stage.
Cooling 1
Solar Adjust? (N)
(IF YES)
Cooling 1
Min Sol (0) K-LUX
Cooling 1
Min Sol (100) K-LUX
(Lower) Setpoint
By 0°F