Datasheet

CPS20.121
C-Series
12V, 30A, SINGLE PHASE INPUT
12. TERMINALS AND WIRING
The terminals are IP20 Finger safe constructed and suitable for field- and factory wiring.
Input and output DC-OK-Signal
Type
screw terminals spring-clamp terminals
Solid wire 0.5-6mm
2
0.15-1.5mm
2
Stranded wire 0.5-4mm
2
0.15-1.5mm
2
American Wire Gauge AWG20-10 AWG26-14
Max. wire diameter 2.8mm (including ferrules) 1.5mm (including ferrules)
Wire stripping length 7mm / 0.28inch 7mm / 0.28inch
Screwdriver 3.5mm slotted or cross-head No 2 3.5mm slotted (to open the spring)
Recommended tightening torque 1Nm, 9lb.in not applicable
Instructions:
a) Use appropriate copper cables that are designed for minimum operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum
90°C for ambient up to 70°C minimum.
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Do not use the unit without PE connection.
e) Unused terminal compartments should be securely tightened.
f) Ferrules are allowed.
Daisy chaining:
Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current
through one terminal pin does not exceed 25A. If the current is higher, use a separate distribution terminal block as
shown in Fig. 12-2.
Fig. 12-1 Daisy chaining of outputs Fig. 12-2 Using distribution terminals
Load
+
-
Power
Supply
+ +
- -
Output
Power
Supply
+ +
- -
Output
max 25A!
continuous
Distribution
Terminals
Load
+
-
Power
Supply
+ +
- -
Output
Power
Supply
+ +
- -
Output
Apr. 2014 / Rev. 1.4 DS-CPS20.121-EN
All parameters are specified at 12V, 30A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
11/26