All parameters are specified at 12V, 30A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
22.12. MOUNTING ORIENTATIONS
Mounting orientations other than all terminals on the bottom require a reduction in continuous output power or a
limitation in the maximum allowed ambient temperature. The amount of reduction influences the lifetime expectancy
of the power supply. Therefore, two different derating curves for continuous operation can be found below:
Curve A1 Recommended output current.
Curve A2 Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 22-4
Mounting
Orientation A
(Standard
orientation)
Power
Supply
Output Current
5A
10 20 30 40
60°C
10A
20A
25A
30A
INPUT OUTPUT
50
A
1
15A
Ambient Temperature
Fig. 22-5
Mounting
Orientation B
(Upside down)
Power
Supply
OUTPUTINPUT
Output Current
5A
10 20 30 40
60°C
10A
20A
25A
30A
50
15A
Ambient Temperature
A
1
A
2
Fig. 22-6
Mounting
Orientation C
(Table-top
mounting)
Output Current
5A
10 20 30 40
60°C
10A
20A
25A
30A
50
15A
Ambient Temperature
A
1
A
2
Fig. 22-7
Mounting
Orientation D
(Horizontal cw)
Power
Supply
OUTPUTINPUT
Output Current
5A
10 20 30 40
60°C
10A
20A
25A
30A
50
15A
Ambient Temperature
A
1
A
2
Fig. 22-8
Mounting
Orientation E
(Horizontal ccw)
Power
Supply
OUTPUTINPUT
Output Current
5A
10 20 30 40
60°C
10A
20A
25A
30A
50
15A
Ambient Temperature
A
1
A
2
26/26